Technical Manual
76
Service
LOSSNAY setting (City Multi only)
F1 F2 F3 F4
unem ecivreS
rosruC
:unem niaM
Test run
Input maintenance info.
Lossnay
Check
Self check
F1 F2 F3 F4
Lossnay
IU address
Lossnay address
Collecting data
F1 F2 F3 F4
Lossnay
Cursor Address
Select:
IU address
Lossnay address
Function Set/Conf/Del.
OFF
City
Multi
Only
P
Service
Button operation
Select "Lossnay" with the F1 or F2 button, and press the button.
[
1
]
Select "Service" from the Main menu (refer to page 19), and press the
button.
This setting is required only when the operation of City Multi units is interlocked with LOSSNAY units. This setting is not avail-
able for the Mr. Slim units. Interlock settings can be made for the indoor unit to which the remote controller is connected. (They
can also be conrmed or deleted.)
note: •
Use the centralized controller to make the settings if it is connected.
• To interlock the operation of the indoor units with the LOSSNAY units, be sure to interlock the addresses
of ALL indoor units in the group and that of the LOSSNAY unit.
[
2
]
When "Lossnay" on the Service menu is selected, the remote controller will auto-
matically begin searching for the registered LOSSNAY addresses of the currently
connected indoor unit.
[
3
]
When the search is completed, the smallest address of the indoor units that are
connected to the remote controller and the address of the interlocked LOSSNAY
unit will appear. "--" will appear if no LOSSNAY unit is interlocked with the indoor
units.
If no settings need to be made, press the
button to go back to the Ser-
vice menu.