Technical Manual
100
System control (for Mr.Slim)
No controll
No controll
No controll
The ability to save : 80%
The ability to save : 70%
The ability to save : 75%
The ability to save : 70%
Damand : 75%
Setting the remote controller
External input
Operation of the outdoor unit
SW1
Orange
1
3
Brown
Red
CNDM
X
X
A
Circuit diagram example
(low noise mode)
B
On-site arrangement
C
External input adapter
(PAC-SC36NA-E)
X: Relay (DC15V. 0.1 or more)
D
Outdoor unit control board
E
Max. 10 m
F
Power supply for relay
SW2
SW3
Orange
1
3
Brown
Red
CNDM
Y
X
X
Y
6. Mode set by external input
6.1 Low -level sound priority mode (Local wiring)
By performing the following modication, operation noise of the outdoor unit can be reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the contact input of an ON/OFF switch is added to
the CNDM connector (option) on the control board of the outdoor unit.
● The ability varies according to the outdoor temperature and conditions, etc.
Complete the circuit as shown when using the external input adapter (PAC-SC36NA-E). (Option)
SW7-1 (Outdoor unit control board): OFF
SW1 ON: Low noise mode
SW1 OFF: Normal operation
A
Circuit diagram example
(Demand function)
C
External input adapter
(PAC-SC36NA-E)
B
On-site arrangement
D
Outdoor unit control board
X: Relay
E
Max. 10 m
(DC15V, 0.1Aor more)
F
Power supply for relay
6.2 On demand control (Local wiring)
By performing the following modication, energy consumption can be reduced to 0–100% of the normal consumption.
The demand function will be activated when a commercially available timer or the contact input of an ON / OFF switch is added
to the CNDM connector (option) on the control board of the outdoor unit.
Complete the circuit as shown when using the external input adapter (PAC-SC36NA-E). (Option)
By setting SW7-1 on the control board of the outdoor unit, the energy consumption (compared to the normal consumption)
can be limited as shown below.
SW7-1 SW2 SW3 Energy consumption
Demand
function
ON
OFF OFF 100%
ON OFF 75%
ON ON 50%
OFF ON 0%(Stop)
■
Operation when using both remote controller settings and external input
When using both the remote controller and external input, the lower setting value will be valid.