MXZ-3C30NA2 Specification Sheet
Specications are subject to change without notice. © 2016 Mitsubishi Electric US, Inc.
Notes:
SPECIFICATIONS: MXZ-3C30NA2, contd.
Indoor Unit Type SEER EER HSPF
COP @
47°F
COP
@ 17°F
Non-ducted
(06 + 06 + 09)
19.0 10.6 10.6 3.90 2.77
Ducted and
Non-ducted
17.6 10.1 10.1 3.77 2.78
Ducted
(09 + 09 + 09)
16.2 9.6 9.6 3.64 2.78
Outdoor
Cooling 14 to 115° F (−10 to 46° C) DB
Heating 5 to 65° F (−15 to 18° C) WB
• Minimum of two Indoor Units must be connected to the MXZ-3C30NA2.
• Minimum installed capacity cannot be less than 12,000 Btu/h.
• Total connected capacity must not exceed 130% of outdoor unit capacity.
• System can operate with only one Indoor Unit turned on.
• Information provided at 208/230V.
• For Reference:
- MXZ-C Technical & Service Manual for detailed specications and additional information per Indoor Unit Combination.
- MXZ Series Multi-Zone Indoor/Outdoor Combination Table for allowed unit combinations.
• Only 1 MVZ may be used on any system.
• When an MVZ is connected, total connected capacity must be 100% or less.
• When an MVZ is connected, no P-Series indoor units can be used (PCA, PLA, or PEAD).
ENERGY EFFICIENCIES:
NOTES:
OPERATING RANGE:
MVZ CONNECTION RULES: