Installation Manual

Eng-21
5. Function settings (continued)
No.43
Indoor temperature correction
Set the correction for the indoor temperature displayed on the
PZ-62DR-E screen by function
No. 37
.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
The correction to
thermistor detection
SW No.
Setting
Function No.
Setting Data
N/A
- -
43
0 -7 K (-12.6 °F/-7 °C )
- - 1 -6 K (-10.8 °F/-6 °C )
- - 2 -5 K (-9 °F/-5 °C )
- - 3 -4 K (-7.2 °F/-4 °C )
- - 4 -3 K (-5.4 °F/-3 °C )
- - 5 -2 K (-3.6 °F/-2 °C )
- - 6 -1 K (-1.8 °F/-1 °C )
- -
7
(Factory setting)
0 K (0 °F/0 °C )
- - 8 +1 K (+1.8 °F/+1 °C )
- - 9 +2 K (+3.6 °F/+2 °C )
- - 10 +3 K (+5.4 °F/+3 °C )
- - 11 +4 K (+7.2 °F/+4 °C )
- - 12 +5 K (+9 °F/+5 °C )
- - 13 +6 K (+10.8 °F/+6 °C )
- - 14
+7 K (+12.6 °F/+7 °C )
No.44
CO2 concentration correction
CO2 concentration displayed on the PZ-62DR-E can be corrected.
This function is available when there is CO2 concentration gap due to
the location of CO2 sensor.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
CO2 concentration
correction
SW No.
Setting
Function No.
Setting Data
N/A
- -
44
0 -500 ppm
- - 1 -400 ppm
- - 2 -300 ppm
- - 3 -200 ppm
- - 4 -100 ppm
- -
5
(Factory setting)
±0 ppm
- - 6 100 ppm
- - 7 200 ppm
- - 8 300 ppm
- - 9 400 ppm
- - 10
500 ppm
No.45
Supply fan monitor threshold
The threshold fan speed of supply fan monitor output can be
selected.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Supply fan monitor
threshold
SW No.
Setting
Function No.
Setting Data
N/A
- -
45
0
(Factory setting)
Fan speed 1 or higher
- - 1 Fan speed 2 or higher
- - 2 Fan speed 3 or higher
- - 3 Fan speed 4
No.46
Exhaust fan monitor threshold
The threshold fan speed of exhaust fan monitor output can be
selected.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Exhaust fan monitor
threshold
SW No.
Setting
Function No.
Setting Data
N/A
- -
46
0
(Factory setting)
Fan speed 1 or higher
- - 1 Fan speed 2 or higher
- - 2 Fan speed 3 or higher
- - 3 Fan speed 4
No.52
Automatic ventilation mode setting 1)
Outdoor and indoor temperature gap
Set one of conditions for By-pass mode in auto ventilation operation,
temperature gap between indoor and outdoor.
This function is N/A from Lossnay unit DIP-SW.
This function can also be set on the Auto By-pass settings screen of
the PZ-62DR-E.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Gap between Indoor
temp. and Outdoor temp.
SW No.
Setting
Function No.
Setting Data
N/A
- -
52
0
(Factory setting)
0 K (0 °F/0 °C ) or more
- - 1
1 K (1.8 °F/1 °C ) or more
- - 2
2 K (3.6 °F/2 °C ) or more
- - 3
3 K (5.4 °F/3 °C ) or more
- - 4
4 K (7.2 °F/4 °C ) or more
- - 5
5 K (9 °F/5 °C ) or more
- - 6
6 K (10.8 °F/6 °C ) or more
- - 7
7 K (12.6 °F/7 °C ) or more
No.53
Automatic ventilation mode setting 2)
The lowest outdoor temperature
Set one of conditions for By-pass mode in auto ventilation operation,
minimum outdoor temperature which comes in indoor directly.
This function is N/A from Lossnay unit DIP-SW.
This function can also be set on the Auto By-pass settings screen of
the PZ-62DR-E.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Outdoor temperature
SW No.
Setting
Function No.
Setting Data
N/A
- -
53
0 50 ˚F (10 ˚C) or more
- - 1 52 ˚F (11 ˚C) or more
- - 2 54 ˚F (12 ˚C) or more
- - 3 55 ˚F (13 ˚C) or more
- - 4 57 ˚F (14 ˚C) or more
- - 5 59 ˚F (15 ˚C) or more
- -
6
(Factory setting)
61 ˚F (16 ˚C) or more
- - 7 63 ˚F (17 ˚C) or more
- - 8 64 ˚F (18 ˚C) or more
- - 9 66 ˚F (19 ˚C) or more
- - 10 68 ˚F (20 ˚C) or more
- - 11 70 ˚F (21 ˚C) or more
- - 12 72 ˚F (22 ˚C) or more
- - 13 73 ˚F (23 ˚C) or more
- - 14 75 ˚F (24 ˚C) or more
- - 15 77 ˚F (25 ˚C) or more