Installation Manual
Eng-14
5. Function settings
Address setting is required when connecting to City Multi and MELANS.
Setting the address
Use the following procedure when setting the address for dedicated
Lossnay.
(The method in determining the addresses will depend on the existing
system. Refer to the appropriate technical documents for details.)
(1) Remove the control box cover.
(2) Turn the address setting switch on the circuit board.
• SW12 indicates the tens digit and SW11 indicates the ones digit.
• The factory setting is “00”.
Address setting switch
SW11 (Ones digit)
Address setting switch
SW12 (Tens digit)
Changing the function selection
switches (SW-2, 5 and 6)
Set the selection switches (SW-2 and 5) to perform the appropriate
function.
* All function except “Trial operation” and “Auto fan speed setting
without Lossnay or M-NET remote controller” can be set also from
the remote controller (PZ-62DR-E). If the function is switched later
using the remote controller, it operates according to the setting on
the remote controller.
1
2
3
4
5
6
7
8
9
10
(SW2)
1
2
3
4
5
6
7
8
9
10
(SW5)
OFF ON
OFF ON
Trial operation
No. 28 Pulse input setting
No. 9 Delay start setting for air conditioner starting
No. 6 Indoor negative pressure setting
No. 7 Indoor positive pressure setting
No. 64 Fan speed for air volume “High” setting
No. 65 Fan speed for air volume “Low” setting
No. 5
Automatic recovery setting after power interruption
N/A
N/A
No. 12 Monitor output setting
No. 17 Exhaust fan setting during air conditioner defrosting
N/A
N/A
No. 66 CO
2 sensor or BMS setting
When connecting the CO2 sensor, Auto fan speed setting without Lossnay or M-NET system controller
N/A
* When the address number has been changed, the data in the
memory is automatically reset.
Change the function settings from the
remote controller PZ-62DR-E.
Please refer to the Instruction book of PZ-62DR-E for how to set the
function settings.
DIP-SW6 is to identify the model for circuit board. When replacing to new circuit board, set the same setting as old one.
(SW6)
SW6-1 SW6-2 SW6-3 SW6-4 SW6-5 SW6-6
LGH-F300RVX2-E OFF OFF ON OFF ON OFF
LGH-F380RVX2-E ON OFF ON OFF ON OFF
LGH-F470RVX2-E OFF ON ON ON ON OFF
LGH-F600RVX2-E ON ON ON ON ON OFF
LGH-F940RVX2-E OFF OFF OFF ON ON OFF
LGH-F1200RVX2-E ON OFF OFF ON ON OFF
* Do not change from factory setting. If changed, please set as factory setting.