Installation Manual
Eng-7
4. Installation method (continued)
Wire connection diagram
* TM1, TM2, TM3, TM4, TB5 shown in dotted lines are eld work.
* Be sure to connect the ground wire.
* A power supply isolator must be installed.
* Always use an isolator for the main switch power connection.
* Select proper circuit breaker according to the electrical current information in the chart below.
* Do not disconnect connectors.
Model
LGH-F300RVX2-E LGH-F380RVX2-E LGH-F470RVX2-E LGH-F600RVX2-E LGH-F940RVX2-E LGH-F1200RVX2-E
Maximum current when
operating [A]
3.40 3.10 4.05 4.15 8.10 8.30
Inrush current after
power supply ON
[A]
10 ms 6.1 12.2
100 ms 3.6 7.2
TM1
1
2
A
B
S
9
10
1
2
Y
Z
TM3
TM4
TB5
TM2
L
N
Operation signals
12 V or 24VDC
or Mr. Slim
Volt-free contact
M-NET transmission
cable
Lossnay remote controller
(Max. 2) and 2nd Lossnay
(Max. 15 units)
Isolator
(Field supply)
Power supply
208-230 V / 60Hz
Shielded wire
Printed Circuit Board
TM1: Terminal block (Power supply)
TM2: Terminal block (External control input)
TM3: Terminal block (Monitor output)
TM4: Terminal block (Transmission cable)
TB5: Terminal block (M-NET transmission cable)