Installation Manual

Eng-25
5. Function settings (continued)
No.73 -78, 87, 88
Airow
Adjust the output of the fan speed. This function can also be set on the Airow settings screen of the PZ-62DR-E.
This function is N/A from Lossnay unit DIP-SW.
PZ-62DR-E
Setting
check
Fan output
Fan
speed
Fan
Function No.
Setting Data
87
0
(Factory setting)
100%
4 SA
1 95%
2 90%
3 85%
4 80%
5 75%
6 70%
7 65%
8 60%
9 55%
10 50%
11 45%
12 40%
13 35%
14 30%
15 25%
73
0 100%
3 SA
1 95%
2 90%
3 85%
4 80%
5
(Factory setting)
75%
6 70%
7 65%
8 60%
9 55%
10 50%
11 45%
12 40%
13 35%
14 30%
15 25%
74
0 100%
2 SA
1 95%
2 90%
3 85%
4 80%
5 75%
6 70%
7 65%
8 60%
9 55%
10
(Factory setting)
50%
11 45%
12 40%
13 35%
14 30%
15 25%
PZ-62DR-E
Setting
check
Fan output
Fan
speed
Fan
Function No.
Setting Data
75
0 100%
1 SA
1 95%
2 90%
3 85%
4 80%
5 75%
6 70%
7 65%
8 60%
9 55%
10 50%
11 45%
12 40%
13 35%
14 30%
15
(Factory setting)
25%
88
0
(Factory setting)
100%
4 EA
1 95%
2 90%
3 85%
4 80%
5 75%
6 70%
7 65%
8 60%
9 55%
10 50%
11 45%
12 40%
13 35%
14 30%
15 25%
76
0 100%
3 EA
1 95%
2 90%
3 85%
4 80%
5
(Factory setting)
75%
6 70%
7 65%
8 60%
9 55%
10 50%
11 45%
12 40%
13 35%
14 30%
15 25%
PZ-62DR-E
Setting
check
Fan output
Fan
speed
Fan
Function No.
Setting Data
77
0 100%
2 EA
1 95%
2 90%
3 85%
4 80%
5 75%
6 70%
7 65%
8 60%
9 55%
10
(Factory setting)
50%
11 45%
12 40%
13 35%
14 30%
15 25%
78
0 100%
1 EA
1 95%
2 90%
3 85%
4 80%
5 75%
6 70%
7 65%
8 60%
9 55%
10 50%
11 45%
12 40%
13 35%
14 30%
15
(Factory setting)
25%
- Fan output percentage of Fan speed 4 cannot be set to lower values than that of Fan speed 3.
Example: When function
No. 73
is set to “5” (75%), the setting data for function
No. 87
can be selected from “0” (100%) to “5” (75%).
- Fan output percentage of Fan speed 3 cannot be set to higher values than that of Fan speed 4, or lower values than that of Fan speed 2.
Likewise, fan output percentage of Fan speed 2 cannot be set to higher values than that of Fan speed 3, or lower values than that of Fan speed 1.
Example: When function
No. 87
is set to “2” (90%) and function
No. 74
is set to “7” (65%), the setting data for function
No. 73
can be
selected from “2” (90%) to “7” (65%).
- Fan output percentage of Fan speed 1 cannot be set to higher values than that of Fan speed 2.
Example: When function
No. 74
is set to “5” (75%), the setting data for function
No. 75
can be selected from “5” (75%) to “15” (25%).
- Function
No. 55
and
No. 56
are available only when Fan output percentage of Fan speed 4 is set to “0” (100%).