Installation Manual
Eng-24
5. Function settings (continued)
No.67
Threshold minutes for PZ-70CSW-E LED
LED turns from orange (MID) to red (HIGH) when the CO2 level is
kept over the limit concentration for decided minutes.
The threshold minutes can be changed.
Refer to the Installation manual of PZ-70CSW-E for more detail.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Threshold minutes for
PZ-70CSW-E LED
SW No.
Setting
Function No.
Setting Data
N/A
- -
67
0 10 min
- - 1 15 min
- -
2
(Factory setting)
20 min
- - 3 25 min
- - 4 30 min
No.68
Threshold concentration for PZ-70CSW-E
LED
The threshold concentration for wall mounted CO2 sensor LED from
green (LOW) to orange (MID) can be changed.
Refer to the Installation manual of PZ-70CSW-E for more detail.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Threshold concentration
for PZ-70CSW-E LED
SW No.
Setting
Function No.
Setting Data
N/A
- -
68
0 1000 ppm
- - 1 1100 ppm
- - 2 1200 ppm
- - 3 1300 ppm
- - 4 1400 ppm
- -
5
(Factory setting)
1500 ppm
- - 6 1600 ppm
- - 7 1700 ppm
- - 8 1800 ppm
- - 9 1900 ppm
- - 10
2000 ppm
No.69
Emergency stop setting
This function can select the priority of Remote OFF signal to CN32.
When the emergency stop is selected and Lossnay receives remote
o signal, Lossnay does not operate Night purge, after cooling or
some other operations until remote o signal stops.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Mode
Lossnay
operation
SW No.
Setting
Function No.
Setting Data
N/A
- -
69
0
(Factory setting)
Emergency
stop
When stopped
by Remote
OFF input,
Night purge,
after cooling
and some other
operation does
NOT work.
- - 1
Normal
stop
When stopped
by Remote
OFF input,
Night purge,
after cooling
and some other
operation does
work.
- When installing the centralized management devices (including the
system controller) in Mitsubishi Electric Air-Conditioner Network
System (MELANS), perform emergency stop by the centralized
management devices. In this case, do not use the function
No. 69
.