Submittal

Specications are subject to change without notice. © 2022 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Job Name:
System Reference: Date:
GENERAL FEATURES
Lossnay
®
cross-ow energy recovery core
Minimal cross contamination between entering and leaving air streams
Stand-alone remote controller (PZ-62DR-EA)
M-NET Connectivity
External input bypass damper control
Stand alone or interlocks connects with all Mitsubishi Electric products
Four fan speeds
High efciency DC Motor
Standard MERV 7 non-woven fabric lter, washable ber
Optional high-efciency MERV 14 and MERV 16 lters
Specications System
Unit Type LGH-F470RVX2-E
Capacity CFM [m
3
/h] 470 [799]
Power source 208/230, 1, 60
Power Consumption kW 0.22 - 0.425
Current A 0.047/0.11
Starting Current A 6.1
MCA A 5.1
Maximum Overcurrent Protection (MOCP) A 15
Fan
Air Volume CFM [m
3
/h] 118- 235-353-470 [ 200-399-599-799]
Type x quantity 9-5/8 In. diameter centrifugal fan
External Static pressure in.WG 0.06–0.25–0.56–1.0
Motor type EC Motor
Exchange Efciency
Temperature % 69-73-77.5-84.5
Enthalpy Cooling % 51.0-57.0- 64.0- 72.0
Enthalpy Heating % 64.0-69.0-75.0-83.0
External nish Galvanized steel sheet
External Dimensions In. [mm] 41-3/8 x 51-5/16 x 15-29/32 [1,051 x 1,302 x 404]
Net weight Lbs [kg] 110 [50]
Energy Transfer Mechanism Lossnay
®
Core
Heat Exchange Material Partition, spacing plate-cellulose ber membrane
Heat Exchange System Air-to-air total heat (sensible heat + latent heat) exchange, no moving parts
Blower Type 9-5/8 In. diameter centrifugal fan
Entering Air Temperature Operation Range °F [°C] 14 to 104 [ -10 to 40]
Sound pressure level dB(A) 40.0–34.0–26.0–20.0
LGH-F470RVX2-E
ENERGY RECOVERY VENTILATION