7. Trial operation (continued)
4. If trouble occurs during trial operation
Symptom Remedy
Lossnay does not operate even
when the operation switch of the
remote controller (PZ-62DR-E) is
pressed.
• Check the power supply. (The specied power supply is single-phase 208-230 V 60 Hz)
• Check for a short circuit or disconnection in the transmission cable. (Check that the voltage between
terminals in the transmission cables is 10 to 13 VDC for the PZ-62DR-E.)
• Check that a clearance of 2” (5 cm) is provided between the transmission cable and the power supply
cable and other transmission cables.
•
Operate Lossnay independently using the trial operation switch (SW2-1) to see if it operates properly or not.
Lossnay operates Check the signal lines
Lossnay doesn’t operate
Check the power supply
• Check if there are three or more remote controller connected. (The maximum is two.)
When M-NET is used, the Lossnay
does not operate by M-NET
system controller.
• Check the power supply. (Specied power supply: single-phase 208-230 V 60 Hz, cable diameter,
switch capacity
• Check if the power supply unit is connected or not, and if the power is supplied or not (For a system
with Lossnay only, it is necessary to install the power supply unit.)
• Check the transmission cable for short-circuit or broken wire (Check if 20 - 30 VDC is detected between
the terminals of transmission cable).
• Check that a clearance of 2” (5 cm) is provided between the transmission cable and the power supply
cable and other transmission cables.
• Operate Lossnay independently to see if it operates properly or not.
Lossnay operates Inspect the transmission cable
Lossnay doesn’t operate
Check the power supply
• Check Lossnay registration condition in the system remote controller.
Air conditioner indoor unit or
external device does not interlock.
• Check if the pulse input switch (SW2-2) is o. (Can be set from PZ-62DR-E)
• Check the overall cable length between the indoor unit or external device and Lossnay. (Refer to
technical manuals or other such documents.)
• Check the connections at the external control input terminal block (TM2).
In the case of voltage charged 12 or 24 VDC output device: Connect to external control input terminals
1 and 2.
In the case of Volt-free contact output device: Connect to external control input terminals
Y
and
Z
.
In the case of Mr. Slim with Slim-Lossnay connection cable: Connect to external control input terminals
1 and
2
.
• Perform the registration using the remote controller for the air conditioner or MELANS. (Refer to the
installation instructions for the remote controller for the air conditioner or MELANS.)
• Check if the delay start time has been set.
• Check the following items after removing the transmission cable from external device.
Operation signal Stop signal
Charged 12 or 24 VDC output device 12 or 24 VDC 0 VDC
Volt-free contact output device
Resistance: 0 Ω Unlimited resistance Ω
Mr. Slim with Slim-Lossnay connection cable. 2 to 6 VDC (pulse signal) 2 to 6 VDC (pulse signal)
• When multiple Lossnay units are connected, check the external signal is inputted into the main unit.
Lossnay does not stop. • Check that the trial operation switch (SW2-1) is set to o.
The inspection indicator lamp (LED
1 Green) in the control box ashes.
1 ash Fault on supply fan motor
Turn the power o and consult
your dealer.
2 ashes Fault on exhaust fan motor
4 ashes Fault on OA thermistor
5 ashes Fault on RA thermistor
6 ashes Fault on supply fan motor
7 ashes Fault on exhaust fan motor
8 ashes Fault on Pre-heater capacity or relay
9 ashes Fault on remote controller communication
10 ashes
Fault on function setting
11 ashes Fault on power supply to remote controller
12 ashes Fault on CO
2 sensor, PZ-70CSB-E or PZ-70CSW-E
• 15 or 30 minutes in the delay start setting, LED lits ON.
• LED blinks just after power supply ON.
The inspection indicator lamp (LED
2 Red ) in the control box ashes.
1 to 8
ashes
Error in M-NET communication Turn o the power and immediately contact your
dealer.
nWhen an error code blinks on the remote controller, follow the procedures shown in the installation and operating manuals provided with the
remote controller.
nIn case of operating Lossnay unit by external input, operate after approximately 2 minutes of turning on the power for the Lossnay.