Installation Manual
Eng-20
5. Function settings (continued)
No.36
Outdoor temperature display setting
Set to display outdoor temperature detected by Lossnay unit
thermistor.
This function is N/A from Lossnay unit DIP-SW.
This function is available only when “Sensor value” is set to “Yes”
(Display) by the remote controller PZ-62DR-E.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Outdoor temperature
display
SW No.
Setting
Function No.
Setting Data
N/A
- -
36
0 N/A
- -
1
(Factory setting)
Available on the screen
of PZ-62DR-E
No.37
Indoor temperature display setting
Set to display indoor temperature detected by Lossnay unit thermistor.
This function is N/A from Lossnay unit DIP-SW.
This function is available only when “Sensor value” is set to “Yes”
(Display) by the remote controller PZ-62DR-E.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Indoor temperature
display
SW No.
Setting
Function No.
Setting Data
N/A
- -
37
0 N/A
- -
1
(Factory setting)
Available on the screen
of PZ-62DR-E
No.38
CO2 concentration display setting
Set to display CO2 concentration when the CO2 sensor (PZ-70CSB-E,
PZ-70CSW-E) is used.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
CO2 concentration
display
SW No.
Setting
Function No.
Setting Data
N/A
- -
38
0 N/A
- -
1
(Factory setting)
Available on the screen
of PZ-62DR-E
- This function is available only when “Sensor value” is set to “Yes”
(Display) by the remote controller PZ-62DR-E.
- When displaying CO2 concentration, supply air temperature cannot
be displayed simultaneously.
- CO2 concentration display shows the value detected by a CO2
sensor connected to Lossnay unit. The value may dier from the
actual indoor CO2 concentration. This function cannot be used as a
measuring instrument.
- The value may signicantly dier from the actual indoor CO2
concentration for approx. 15 minutes after starting operation.
- When 3rd party’s CO2 sensor is connected, CO2 concentration is
not displayed on PZ-62DR-E screen.
No.39
Calculated supply air temperature display
setting
Set to display calculated supply air temperature or not.
This function is N/A from Lossnay unit DIP-SW.
In addition, this function is available only when “Sensor value” is set
to “Yes”(Display) by the remote controller PZ-62DR-E.
CO2 concentration and supply air temperature can not be displayed
at the same time.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Calculated supply air
temperature display
SW No.
Setting
Function No.
Setting Data
N/A
- -
39
0
(Factory setting)
N/A
- - 1
Available on the screen
of PZ-62DR-E
- CO2 concentration and supply air temperature can not be displayed
at the same time.
No.40, 41
Temperature exchange eciency
setting
Set the 10 digit of temperature exchange eciency which is used to
calculate supply air temperature.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
10 digit of temperature
exchange eciency
SW No.
Setting
Function No.
Setting Data
N/A
- -
40
0 0
- - 1 1
- - 2 2
- - 3 3
- - 4 4
- - 5 5
- - 6 6
- -
7
(Factory setting)
7
- - 8 8
- - 9 9
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
1 digit of temperature
exchange eciency
SW No.
Setting
Function No.
Setting Data
N/A
- -
41
0
(Factory setting)
0
- - 1 1
- - 2 2
- - 3 3
- - 4 4
- - 5 5
- - 6 6
- - 7 7
- - 8 8
- - 9 9
No.42
Outdoor temperature correction
Set the correction for the outdoor temperature displayed on the
PZ-62DR-E screen by function
No. 36
.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
The correction to
thermistor detection
SW No.
Setting
Function No.
Setting Data
N/A
- -
42
0 -7 K (-12.6 °F/-7 °C )
- - 1 -6 K (-10.8 °F/-6 °C )
- - 2 -5 K (-9 °F/-5 °C )
- - 3 -4 K (-7.2 °F/-4 °C )
- - 4 -3 K (-5.4 °F/-3 °C )
- - 5 -2 K (-3.6 °F/-2 °C )
- - 6 -1 K (-1.8 °F/-1 °C )
- -
7
(Factory setting)
0 K (0 °F/0 °C )
- - 8 +1 K (+1.8 °F/+1 °C )
- - 9 +2 K (+3.6 °F/+2 °C )
- - 10 +3 K (+5.4 °F/+3 °C )
- - 11 +4 K (+7.2 °F/+4 °C )
- - 12 +5 K (+9 °F/+5 °C )
- - 13 +6 K (+10.8 °F/+6 °C )
- - 14 +7 K (+12.6 °F/+7 °C )