Submittal
Specications are subject to change without notice. © 2022 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Job Name:
System Reference: Date:
GENERAL FEATURES
• Lossnay
®
cross-ow energy recovery core
• Minimal cross contamination between entering and leaving air streams
• Stand-alone remote controller (PZ-62DR-EA)
• M-NET Connectivity
• External input bypass damper control
• Stand alone or interlocks connects with all Mitsubishi Electric products
• Four fan speeds
• High efciency DC Motor
• Standard MERV 7 non-woven fabric lter, washable ber
• Optional high-efciency MERV 14 and MERV 16 lters
Specications System
Unit Type LGH-F380RVX2-E
Capacity CFM [m
3
/h] 380 [646]
Power source 208/230, 1, 60
Power Consumption kW 0.165 - 0.34
Current A 0.02/0.065
Starting Current A 6.1
MCA A 3.9
Maximum Overcurrent Protection (MOCP) A 15
Fan
Air Volume CFM [m
3
/h] 95- 190-285-380 [ 161-323-484-646]
Type x quantity 8-3/4 In. diameter centrifugal fan
External Static pressure in.WG 0.06–0.22–0.48–0.86
Motor type EC Motor
Exchange Efciency
Temperature % 65-69.5-75-82
Enthalpy Cooling % 49.0-53.5- 60.0- 68.0
Enthalpy Heating % 61.0-65.5-71.0-78.0
External nish Galvanized steel sheet
External Dimensions In. [mm] 39-13/32 x 42 x 15-29/32 [1,001 x 1,066 x 404]
Net weight Lbs [kg] 90 [41]
Energy Transfer Mechanism Lossnay
®
Core
Heat Exchange Material Partition, spacing plate-cellulose ber membrane
Heat Exchange System Air-to-air total heat (sensible heat + latent heat) exchange, no moving parts
Blower Type 8-3/4 In. diameter centrifugal fan
Entering Air Temperature Operation Range °F [°C] 14 to 104 [ -10 to 40]
Sound pressure level dB(A) 38.0–31.0–24.0–19.0
LGH-F380RVX2-E
ENERGY RECOVERY VENTILATION