Installation Manual
Eng-27
5. Function settings (continued)
No.93
CO2 sensor correction
CO2 concentration can be corrected when PZ-70CSW-E or PZ-
70CSB-E is connected.
In this function, the control value of CO2 level is corrected.
On the other hand,
No. 44
is change the displayed CO2 level only.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
CO2 sensor analogue
correction
SW No.
Setting
Function No.
Setting Data
N/A
- -
93
0 -250 ppm
- - 1 -200 ppm
- - 2 -150 ppm
- - 3 -100 ppm
- - 4 -50 ppm
- -
5
(Factory setting)
±0 ppm
- - 6 50 ppm
- - 7 100 ppm
- - 8 150 ppm
- - 9 200 ppm
- - 10
250 ppm
No.100
Initialization (No.1~99)
Set to initialize the remote PZ-62DR-E setting.
All settings which are changed by users are cancelled.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Initialization
SW No.
Setting
Function No.
Setting Data
N/A
- -
100
0
(Factory setting)
N/A
- - 1 Available