Installation Manual

Eng-16
No Function
Setting Data
Factory
setting
DIP-SW
No.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
52
Automatic ventilation mode
setting 1)
Outdoor and indoor
temperature gap
Setting Data 0 to 7 --
>
Temperature gap 0 K (0˚F) to 7 K (12.6˚F) 0
53
Automatic ventilation mode
setting 2)
The lowest outdoor
temperature setting
Setting Data 0 to 15 --
>
Lowest outdoor temperature 50˚F (10˚C) to 77˚F (25˚C) 6
54
Automatic ventilation mode
setting 3)
The lowest indoor temperature
setting
Setting Data 0 to 15 --
>
Lowest indoor temperature 59˚F (15˚C) to 86˚F (30˚C) 1
55
Supply fan power up for Fan
speed 4
N/A
1 level up 2 level up 3 level up 4 level up
0
56
Exhaust fan power up for Fan
speed 4
N/A
1 level up 2 level up 3 level up 4 level up
0
60
Pre-heater output setting 1)
ON temperature
32 ˚F
(0 ˚C)
30 ˚F
(-1 ˚C)
28 ˚F
(-2 ˚C)
27 ˚F
(-3 ˚C)
25 ˚F
(-4 ˚C)
23 ˚F
(-5 ˚C)
21 ˚F
(-6 ˚C)
19 ˚F
(-7 ˚C)
0
61
Pre-heater output setting 2)
OFF interval
1 hr 2 hrs 3 hrs 4 hrs 5 hrs 0
62
LED usage setting for
PZ-70CSW-E during non
operation
Unlit Lit 0
64
Fan speed for air volume “High”
input
Dip-SW
priority
Fan speed 4 Fan speed 3
0 2-6
65
Fan speed for air volume “Low”
input
Dip-SW
priority
Fan speed 2 Fan speed 1
0 2-7
66 CO
2
sensor or BMS setting
Dip-SW
priority
N/A
3rd par-
ty’s CO
2
seonsor
BMS
Pattern Z
CO
2
sensor
PZ-70CSW-E
CO
2
sensor
PZ-70CSB-E
0
5-6
5-7
5-8
67
Threshold minutes for
PZ-70CSW-E LED
10 min 15 min 20 min 25 min 30 min 2
68
Threshold concentration for
PZ-70CSW-E LED
1000 ppm 1100 ppm 1200 ppm 1300 ppm 1400 ppm 1500 ppm 1600 ppm 1700 ppm
1800
ppm
1900
ppm
2000
ppm
5
69 Emergency stop setting
Emergency
stop
Normal
stop
0
73
Airow setting for supply fan
speed 3
100 % 95 % 90 % 85 % 80 % 75 % 70 % 65 % 60 % 55 % 50 % 45 % 40 % 35 % 30 % 25 %
5
74
Airow setting for supply fan
speed 2
100 % 95 % 90 % 85 % 80 % 75 % 70 % 65 % 60 % 55 % 50 % 45 % 40 % 35 % 30 % 25 %
10
75
Airow setting for supply fan
speed 1
100 % 95 % 90 % 85 % 80 % 75 % 70 % 65 % 60 % 55 % 50 % 45 % 40 % 35 % 30 % 25 %
15
76
Airow setting for exhaust fan
speed 3
100 % 95 % 90 % 85 % 80 % 75 % 70 % 65 % 60 % 55 % 50 % 45 % 40 % 35 % 30 % 25 %
5
77
Airow setting for exhaust fan
speed 2
100 % 95 % 90 % 85 % 80 % 75 % 70 % 65 % 60 % 55 % 50 % 45 % 40 % 35 % 30 % 25 %
10
78
Airow setting for exhaust fan
speed 1
100 % 95 % 90 % 85 % 80 % 75 % 70 % 65 % 60 % 55 % 50 % 45 % 40 % 35 % 30 % 25 %
15
83
Filter maintenance interval
setting - Thousands digit
0 1 2 3 4 5 6 7 8 9
3
84
Filter maintenance interval
setting - Hundreds digit
0 1 2 3 4 5 6 7 8 9
0
85
Lossnay core maintenance
interval setting - Thousands
digit
0 1 2 3 4 5 6 7 8 9
6
86
Lossnay core maintenance
interval setting - Hundreds digit
0 1 2 3 4 5 6 7 8 9
0
87
Airow setting for supply fan
speed 4
100 % 95 % 90 % 85 % 80 % 75 % 70 % 65 % 60 % 55 % 50 % 45 % 40 % 35 % 30 % 25 %
0
88
Airow setting for exhaust fan
speed 4
100 % 95 % 90 % 85 % 80 % 75 % 70 % 65 % 60 % 55 % 50 % 45 % 40 % 35 % 30 % 25 %
0
89
CO
2
sensor setting - maximum
side - Hundreds digits
600 ppm 700 ppm 800 ppm 900 ppm 1000 ppm 1100 ppm 1200 ppm 1300 ppm
1400
ppm
1500
ppm
1600
ppm
1700
ppm
1800
ppm
1900
ppm
2000
ppm
4
90
CO
2
sensor setting - maximum
side - tens digits
0 ppm 50 ppm
0
91
CO
2
sensor setting - minimum
side - Hundreds digits
300 ppm 400 ppm 500 ppm 600 ppm 700 ppm 800 ppm 900 ppm 1000 ppm
1100
ppm
1200
ppm
1300
ppm
1400
ppm
1500
ppm
1600
ppm
1700
ppm
1
92
CO
2
sensor setting - minimum
side - tens digits
0 ppm 50 ppm
1
93 CO
2
sensor correction
-250 ppm -200 ppm -150 ppm -100 ppm -50 ppm 0 ppm 50 ppm 100 ppm
150
ppm
200
ppm
250
ppm
5
100
Initialization (No.1
99) N/A Initialize 0
This table shows the summary of function settings. Please refer to the following pages for more details.
The functions indicated with “N/A” in the “DIP-SW No.” column are available only when using with remote controller PZ-62DR-E.
PZ-62DR-E can set Night purge setting (No.30), By-pass setting (No.52, 53, 54 ), CO
2
sensor setting (No.89, 90, 91, 92), Filter maintenance interval setting
(No.83, 84), Lossnay core maintenance interval setting (No. 85, 86) and Airow setting (No. 73-78, 87, 88) by di󰀨erent way more easily.
Refer to the remote controller PZ-62DR-E operation manual for more detail.
5. Function settings (continued)