Installation Manual
Eng-11
4. Installation method (continued)
• Install the duct heater separated from the product by a
distance of 2.2 yd (2 m) or more.
Failure to do so may result in equipment damage due to the
transmission of residual heat from the heater.
• Ensure that the duct heater and Lossnay are wired and that
the Lossnay function settings have been congured, and then
always check operation by trial operation.
• For the duct heater output, see function setting
No. 60
and
No. 61
.
When using After-heater output signal, the wiring should be as shown
by the following picture.
For the heater, observe the cautions listed in Pre-heater.
5
When switching fan speed externally
(when a sensor or other equipment is connected)
Using a eld supply sensor, etc., make connection by inserting the
optional remote controller adapter (PAC-SA88HA-E or PAC-725AD)
in the connector CN17 (Red) as shown by the gure.
Lossnay will operate at the fan speed following the table below,
regardless of the remote controller setting.
CN17 (Red) Fan speed
1-2 (Brown-Red) 4
1-3 (Brown-Orange) 3
1-4 (Brown-Yellow) 2
1-5 (Brown-Green) 1
nExample “Fan speed 4”
Use this in such a way that it ventilates at low fan speed normally,
and when the external sensor detects contamination of indoor air, or
SW1 is on, it changes to high fan speed operation.
When multiple Lossnay units are controlled by one input, PZ-62DR-E
is necessary.
The signal has to be inputted into main unit referring to 3.
Cannot be used in conjunction with the following functions:
- To change fan speed by 0 - 10 VDC input.
- Connecting CO2 sensor PZ-70CSB-E or PZ-70CSW-E.
Relay
2.2 yd (2 m) or more
Power Supply
for heater
Power Supply
for relay
TM3
Max. 230 VAC, 1 A
24 VDC, 1 A
Min. 208 VAC, 100 mA
5 VDC, 100 mA
9
10
Lossnay
SA
OA
SW1
CN17
Field supply sensor, etc.
Remote controller adapter
(Optional) PAC-SA88HA-E
or PAC-725AD
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
Not used. Insulate completely.
Max wiring length 11 yd (10 m)
Lossnay
control board
Fan speed
selection
6
When switching By-pass externally.
Establish the wire connection by inserting the optional remote
controller adapter (PAC-SA88HA-E or PAC-725AD) in the connector
CN26 (White).
With SW1 is “ON”, the ventilation mode of Lossnay is changed to the
By-pass ventilation regardless of the setting on the remote controller.
When multiple Lossnay units are controlled by one input, PZ-62DR-E
is necessary.
The signal has to be inputted into main unit referring to 3.
* When the outdoor air temperature drops lower than 46˚F (8˚C), it
changes to the heat recovery ventilation. (In this case, ventilation
mode icon on the display of the remote controller does not change
from the previous mode, it might be dierent from the actual unit
operation.)
7
To change fan speed by 0 - 10 VDC input
Establish the wire connection by inserting the optional remote
controller adapter (PAC-SA88HA-E or PAC-725AD) in the connector
CN26 (White).
To change fan speed by 0 - 10 VDC input, the wiring should be as
shown by the above picture. Refer to function settings
No. 66
for
more details.
When multiple Lossnay units are controlled by one input, PZ-62DR-E
is necessary.
The signal has to be inputed into main unit referring to 3.
Cannot be used in conjunction with the following functions:
- Switching fan speed externally (CN17).
- Connecting CO2 sensor PZ-70CSB-E or PZ-70CSW-E.
CAUTION
• Make sure of correct polarity.
• Do not apply voltages higher than 10 VDC.
SW1
CN26
SW1: By-pass ventilation operation switch
(When closed: For By-pass ventilation operation)
Remote controller adapter
(Optional) PAC-SA88HA-E
or PAC-725AD
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
Lossnay
control board
Fan speed/
Ventilation
mode selection
Max wiring length 11 yd (10 m)
Not used. Insulate completely.
e.g. 3rd party CO
2 sensor
CN26
Remote controller adapter
(Optional) PAC-SA88HA-E
or PAC-725AD
Yellow 4 (0 - 10 VDC)
Green 5 (COM)
Lossnay
control board
Fan speed/
Ventilation
mode selection
External
device
Max wiring length 11 yd (10 m)
Brown 1
Red 2
Orange 3
Not used. Insulate
completely.