Service Manual

─ 5 ─
Model name
Input
power
(W)
Air volume
Specific
Fan
power
Static
pressure
Exchange efficiency (%)
Noise
(dB)
Dia. of the
centrifugal
fan
(Inch (mm))
Weight
(CFM) (CMH)
(W/CFM)
(InH2O)
(Pa)
Tempe-
rature
Enthalpy
(lbs) (kg)
Heating Cooling
LGH-F300RVX2-E 235 300 510 0.78 1.00 250 65.5 63.0 50.0 37.0 8 3/4 (220) 75 34
LGH-F380RVX2-E 340 380 646 0.89 0.86 215 65.0 61.0 49.0 38.0 9 5/8 (245) 90 41
LGH-F470RVX2-E 425 470 799 0.91 1.00 250 69.0 64.0 51.0 40.0 9 5/8 (245) 110 50
LGH-F600RVX2-E 515 600 1019 0.86 0.86 215 67.0 64.0 50.0 41.0 9 5/8 (245) 123 56
LGH-F940RVX2-E 850 940 1597 0.91 1.00 250 69.0 64.0 51.0 43.0 9 5/8 (245) 225 102
LGH-F1200RVX2-E 1030 1200 2039 0.86 0.86 215 67.0 64.0 50.0 43.0 9 5/8 (245) 251 114
* The above values apply during energy recovery ventilation when the fan speed is set to Fan speed 4 at the rating
pressure loss and 230 V / 60 Hz.
* For the specifications at the other frequency or voltages, see the spec. sheets.
* The values given in the table for the noise level reflect the levels measured at a position 4.9 feet (1.5 m) immedi-
ately below the unit in an anechoic chamber.
* Noise change or increase may occur because of the Bypass-Automatic function or Automatic fan speed change
by timer setting and/or other functions.
* Temperature Exchange efficiency (%) are average of summer and winter condition.
* Mitsubishi Electric measures products according to ISO 16494:2014, therefore characteristic values are mea-
sured by chamber method.
* On-site commissioning measurements by pitot tube method could be as much 20% different from ISO test room
conditions. If the measuring point is close to sources of turbulence like bends, contractions and dampers, etc., it is
difficult to measure air volume correctly. A straight duct length more than 10 D (D=duct diameter) from the source
of turbulence is recommended for correct measurement. On-site measurement should therefore be measured
in accordance with BSRIA guideline (Commissioning Air System. Application procedures for buildings AG3/89.3
(2001)).
Remote controller
Model name PZ-62DR-EA PZ-43SMF-E
Power supply requirement 12 V DC (Supplied from Lossnay unit)
Power consumption 0.3 W
Transmission cable
Non polarized 2-core cable (AWG 22 (0.3 mm
2
) sheathed cable)
Total wiring length 219 yd. (200 m) maximum
Number of controllable Lossnay units 15 Lossnay units maximum (Max. 2 remote controllers installable)
Environmental condition Temperature: 32 to 104ºF (0 to 40°C)
Humidity: 30% to 90% relative humidity (no condensation)
Size 4 22/32 x 4 22/32 x 3/4 inch
(120 x 120 x 19 mm)
4 22/32 x 2 3/4 x 19/32 inch
(120 x 70 x 15 mm)
Weight 9/16 lbs (0.25 kg) 7/32 lbs (0.10 kg)