Installation Manual
Eng-10
4. Installation method (continued)
• If the input is pulse signal, move the pulse input switch [SW2-2]
to the ON position. (Refer to function settings
No. 28
)
• When level signal is selected, the signal width has to be more
than 10 seconds for ON and OFF .
• When pulse signal is selected, a pulse width has to be at least
200 m sec. to turn Lossnay ON, and 10 sec. interval is necessary
to next output.
• The wiring should be as shown by the following picture.
CAUTION
• If an optocoupler or any other type of polar coupler is used at
the Volt-free contact, connect the positive side to
Y
and the
negative side to
Z
.
3
When operating multiple Lossnay units
In the case that all Lossnay units are the same LGH-FRVX2-E series,
up to 15 multiple units can be operated at the same time.
1) Connect the Lossnay unit from Unit 1 to Unit 2, and from Unit 2 to
Unit 3 and so on up to a maximum of 15 units using a transmission
cable.
Wire type: two-core sheathed cable
Wire diameter: AWG 22 (0.3 mm
2)
2) When it is interlocked with an external device, set the Lossnay unit
which has external signal input to “Main”.
CAUTION
TM4, TB5
Note
• Do not tighten screws of terminal block with a torque larger
than 1.2 N・m. It could damage the circuit board.
• When connecting multiple cables to the terminal, use round
terminal.
• Solid wire (single-stranded wire) cannot be connected.
When the external device has an Volt-free contact signal
Y Z
1 2
Lossnay external
control input
(TM2)
AWG 20 (0.5 mm
2
) to AWG 15 (1.5 mm
2
)
sheathed PVC cable
External device
Volt-free contact
Maximum 547 yd (500 m)
Operating switch for
external device
Power supply
External
device
Lossnay
Remote controller
(PZ-62DR-E)
Lossnay
MAX 15 units
Power supply
Power supply
Power supply
Lossnay
Connect to
remote controller
(PZ-62DR-E)
Connect to
third Lossnay
21
21
Transmission cable
First
Lossnay
Second
Lossnay
TM4
TM4
✓
• Only one unit can be set as main Lossnay. The operating signal
and pulse signal of the external device can be connected to
Main Lossnay only.
• Connect the power supply cable to each Lossnay unit.
• When setting the Lossnay address for use with a Mitsubishi
Electric Air-Conditioner Network System (MELANS) etc., the
Lossnay with the smallest address in the group will be the
Main Lossnay. When not setting the address, set the address
to “1” for only one unit in the group. The Lossnay with an
address of “1” is the Main Lossnay. (Refer to “Setting the
address” on the section 5 for more detail.)
4
Signal output from Lossnay unit
Set DIP-SW or Function setting on PZ-62DR-E as following table
depending on the necessary output signal from Lossnay unit. For
more information of signal output, see function settings
No. 12
to
No. 16
.
DIP-SW setting
Function setting on
PZ-62DR-E
Signal output
SW5-1 SW5-2
- -
12
0 Dip-SW priority
OFF OFF 1 Operation monitor
ON OFF 2 Malfunction monitor
OFF ON 3 By-pass monitor
ON ON 4 Supply fan operation monitor
N/A N/A 5 Exhaust fan operation monitor
N/A N/A 6 Pre-heater signal output
N/A N/A 7 After-heater signal output
• Do not tighten screws of terminal block with a torque larger than 0.5
N・m. It could damage the circuit board.
• When connecting multiple cables to the terminal, use round terminal.
• If multiple output signals are necessary, use optional signal output
terminal (PZ-N4GS-E).
When using Pre-heater output signal, the wiring should be as shown
by the following picture.
CAUTION
• Failure to follow below instructions, it could cause a re.
• Choose a OA pre-heater which can control the heater outlet air
temperature even both the air ow is maximum and minimum.
Otherwise it could fall the supply fan into intermittent
operation.
• Select a duct heater in compliance with local and national laws,
ordinances, and standards.
• Select a duct heater that is tested by a certication body.
• Always select a heater that is equipped with a non-self-
resetting safety device.
• Do not directly supply power from the Lossnay unit to the duct
heater. Doing so could cause re.
• Install a circuit breaker for the duct heater in compliance with
all applicable laws, ordinances, and standards.
9
10
Indicator
External device
etc.
Power Supply for
external device
TM3
Max. 230 VAC, 1 A
24 VDC, 1 A
Min. 208 VAC, 100 mA
5 VDC, 100 mA
9
10
Relay
Pre-heater
2.2 yd (2 m or more)
Power Supply
for heater
Power Supply
for relay
TM3
Max. 230 VAC, 1 A
24 VDC, 1 A
Min. 208 VAC, 100 mA
5 VDC, 100 mA
SA
OA
Lossnay