Submittal
Specications are subject to change without notice. © 2022 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Job Name:
System Reference: Date:
GENERAL FEATURES
• Lossnay
®
cross-ow energy recovery core
• Minimal cross contamination between entering and leaving air streams
• Stand-alone remote controller (PZ-62DR-EA)
• M-NET Connectivity
• External input bypass damper control
• Stand alone or interlocks connects with all Mitsubishi Electric products
• Four fan speeds
• High efciency DC Motor
• Standard MERV 7 non-woven fabric lter, washable ber
• Optional high-efciency MERV 14 and MERV 16 lters
Specications System
Unit Type LGH-F1200RVX2-E
Capacity CFM [m
3
/h] 1,200 [2,039]
Power source 208/230, 1, 60
Power Consumption kW 0.54 - 1.03
Current A 0.094/0.24
Starting Current A 12.2
MCA A 10.4
Maximum Overcurrent Protection (MOCP) A 15
Fan
Air Volume CFM [m
3
/h] 300- 600-900-1,200 [ 510-1,019-1,529-2,039]
Type x quantity 9-5/8 In. diameter centrifugal fan
External Static pressure in.WG 0.05–0.22–0.48–0.86
Motor type EC Motor
Exchange Efciency
Temperature % 67-73-76.5-81
Enthalpy Cooling % 50.0-56.5- 64.5- 71.0
Enthalpy Heating % 64.0-68.5-74.5-80.0
External nish Galvanized steel sheet
External Dimensions In. [mm] 50-1/8 x 49-15/16 x 31-13/16 [1,272 x 1,267 x 808]
Net weight Lbs [kg] 251 [114]
Energy Transfer Mechanism Lossnay
®
Core
Heat Exchange Material Partition, spacing plate-cellulose ber membrane
Heat Exchange System Air-to-air total heat (sensible heat + latent heat) exchange, no moving parts
Blower Type 9-5/8 In. diameter centrifugal fan
Entering Air Temperature Operation Range °F [°C] 14 to 104 [ -10 to 40]
Sound pressure level dB(A) 43.0–37.0–28.0–20.0
LGH-F1200RVX2-E
ENERGY RECOVERY VENTILATION