Service Manual

─ 39 ─
(5) Temperatures and thermistor resistance table
(6) Motor resistance table
Cautions:
Before disconnecting the motor connectors, make sure that the power is turned OFF and the circuit
board is discharged adequately.
Even after the power supply is cut off, the capacitor is charged. Therefore, high voltage is applied to
the motor for a while. Make sure that the LEDs on the circuit boards are turned OFF before starting
work.
Never touch the circuit board while the power is ON. It causes electric shock and failure of the unit.
Replace the fan motor in the following cases.
[1] If it is hard to rotate the motor shaft by hand
[2] If the resistance between the motor leads is significantly different from the values specified in the table below
*Before measuring the resistance, the motor connectors must be disconnected from the circuit board.
<LGH-F300RVX2-E, LGH-F380RVX2-E>
Pin No.
Supply fan motor 3-1 3-4 3-5 3-6
Exhaust fan motor 4-1 4-5 4-6 4-7
Normal resistance About 815 kΩ About 40 kΩ About 105 kΩ ∞ kΩ
<LGH-F470RVX2-E, LGH-F600RVX2-E, LGH-F940RVX2-E, LGH-F1200RVX2-E>
Pin No.
Supply fan motor 3-1 3-4 3-5 3-6
Exhaust fan motor 4-1 4-5 4-6 4-7
Normal resistance ∞ kΩ About 50 kΩ About 150 kΩ ∞ kΩ
Temperature
Resistance
value (kΩ)
Temperature
Resistance
value (kΩ)
Temperature
Resistance
value (kΩ)
Temperature
Resistance
value (kΩ)
Temperature
Resistance
value (kΩ)
(°F) (°C) (°F) (°C) (°F) (°C) (°F) (°C) (°F) (°C)
-22 -30 64.2 to ∞ 19.4 -7 19.4 46.4 8 9.9 73.4 23 5.4
100.4
38 3.1
21.2 -6 18.5 48.2 9 9.5 75.2 24 5.2
102.2
39 3.0
-4.0 -20 37.2 23.0 -5 17.7 50.0 10 9.1 77.0 25 5.0
104.0
40 2.9
-2.2 -19 35.3 24.8 -4 16.9 51.8 11 8.7 78.8 26 4.8
105.8
41 2.8
-0.4 -18 33.5 26.6 -3 16.1 53.6 12 8.4 80.6 27 4.6
107.6
42 2.7
1.4 -17 31.8 28.4 -2 15.4 55.4 13 8.0 82.4 28 4.5
109.4
43 2.6
3.2 -16 30.2 30.2 -1 14.7 57.2 14 7.7 84.2 29 4.3 111.2 44 2.5
5.0 -15 28.7 32.0 0 14.0 59.0 15 7.4 86.0 30 4.2 113.0 45 2.5
6.8 -14 27.3 33.8 1 13.4 60.8 16 7.1 87.8 31 4.0 114.8 46 2.4
8.6 -13 26.0 35.6 2 12.8 62.6 17 6.8 89.6 32 3.9 116.6 47 2.3
10.4 -12 24.7 37.4 3 12.3 64.4 18 6.6 91.4 33 3.7 118.4 48 2.2
12.2 -11 23.6 39.2 4 11.8 66.2 19 6.3 93.2 34 3.6
120.2
49 2.2
14.0 -10 22.4 41.0 5 11.3 68.0 20 6.1 95.0 35 3.5
122.0
50 2.1
15.8 -9 21.4 42.8 6 10.8 69.8 21 5.8 96.8 36 3.3
17.6 -8 20.4 44.6 7 10.3 71.6 22 5.6 98.6 37 3.2 194 90 0 to 0.7
* Measure the return air (RA) thermistor resistance across pin No. 1 and 2 of CN5, and the outdoor air (OA)
thermistor resistance across pin No. 1 and 3 of CN7.
Supply fan motor connector
Exhaust fan motor connector