Installation Manual

Eng-26
5. Function settings (continued)
No.83, 84
Filter maintenance interval setting
Filter cleaning sign is displayed on the remote controller according to
the set interval in this function.
The interval can be set from 100 hrs to 9900 hrs depending on the
site situation.
This function can also be set on the Maintenance interval settings
screen of the PZ-62DR-E.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Filter maintenance interval
setting - Thousands digit
SW No.
Setting
Function No.
Setting Data
N/A
- -
83
0 0
- - 1 1
- - 2 2
- -
3
(Factory setting)
3
- - 4 4
- - 5 5
- - 6 6
- - 7 7
- - 8 8
- - 9 9
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Filter maintenance interval
setting - Hundreds digit
SW No.
Setting
Function No.
Setting Data
N/A
- -
84
0
(Factory setting)
0
- - 1 1
- - 2 2
- - 3 3
- - 4 4
- - 5 5
- - 6 6
- - 7 7
- - 8 8
- - 9 9
No.85, 86
Lossnay core maintenance interval
setting
Lossnay core maintenance sign is displayed on the remote controller
according to the set interval in this function.
The interval can be set from 100 hrs to 9900 hrs depending on the
site situation.
This function can also be set on the Maintenance interval settings
screen of the PZ-62DR-E.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Lossnay core maintenance
interval setting - Thousands digit
SW No.
Setting
Function No.
Setting Data
N/A
- -
85
0 0
- - 1 1
- - 2 2
- - 3 3
- - 4 4
- - 5 5
- -
6
(Factory setting)
6
- - 7 7
- - 8 8
- - 9 9
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Lossnay core maintenance
interval setting - Hundreds digit
SW No.
Setting
Function No.
Setting Data
N/A
- -
86
0
(Factory setting)
0
- - 1 1
- - 2 2
- - 3 3
- - 4 4
- - 5 5
- - 6 6
- - 7 7
- - 8 8
- - 9 9
No.89, 90
CO2 sensor setting - maximum side
It is possible to set the CO2 concentration which fan speed turn into
4.
When it is necessary to set 50 ppm, set Function
No. 90
as 1.
This function can also be set on the CO2 control setting screen of the
PZ-62DR-E.
(For example, the target is 950 ppm, Function
No. 89
is 3 and
No. 90
is 1.)
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
CO2 sensor setting
- maximum side -
Hundreds digit
SW No.
Setting
Function No.
Setting Data
N/A
- -
89
0 600 ppm
- - 1 700 ppm
- - 2 800 ppm
- - 3 900 ppm
- -
4
(Factory setting)
1000 ppm
- - 5 1100 ppm
- - 6 1200 ppm
- - 7 1300 ppm
- - 8 1400 ppm
- - 9 1500 ppm
- - 10 1600 ppm
- - 11 1700 ppm
- - 12 1800 ppm
- - 13 1900 ppm
- - 14 2000 ppm
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
CO2 sensor setting -
maximum side
- Tens
digits
SW No.
Setting
Function No.
Setting Data
N/A
- -
90
0
(Factory setting)
0 ppm
- - 1 50 ppm
No.91, 92
CO2 sensor setting - minimum side
It is possible to set the CO2 concentration which fan speed turn into
1.
When it is necessary to set 50 ppm, set Function
No. 92
as 1.
This function can also be set on the CO2 control setting screen of the
PZ-62DR-E.
(For example, the target is 950 ppm, Function
No. 91
is 6 and
No. 92
is 1.)
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
CO2 sensor setting
- minimum side -
Hundreds digits
SW No.
Setting
Function No.
Setting Data
N/A
- -
91
0 300 ppm
- -
1
(Factory setting)
400 ppm
- - 2 500 ppm
- - 3 600 ppm
- - 4 700 ppm
- - 5 800 ppm
- - 6 900 ppm
- - 7 1000 ppm
- - 8 1100 ppm
- - 9 1200 ppm
- - 10 1300 ppm
- - 11 1400 ppm
- - 12 1500 ppm
- - 13 1600 ppm
- - 14 1700 ppm
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
CO2 sensor setting -
minimum side
- Tens
digits
SW No.
Setting
Function No.
Setting Data
N/A
- -
92
0 0 ppm
- -
1
(Factory setting)
50 ppm