Installation Manual

Eng-19
5. Function settings (continued)
No.28
Pulse input setting
Set external input signal type from external device for TM2.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Pulse input setting
SW No.
Setting
Function No.
Setting Data
SW2-2
- -
28
0
(Factory setting)
DIP-SW priority
OFF
(Factory setting)
1 NOT pulse input
ON 2 Pulse input
When pulse signal is selected,
and
No. 19
are not available.
Keep factory settings for
and
No. 19
.
Either interlocking with City multi or Mr. Slim is not possible.
No.30
Night-purge setting 1)
Air volume
Set fan speed during Night-purge. To use Night-purge function, it is
necessary to set
No. 30
,
No. 31
,
No. 32
correctly.
This function is N/A from Lossnay unit DIP-SW.
It can also be set on the PZ-62DR-E’s Ventilation settings screen.
When using PZ-62DR-E and AE-200A together, set all conditions
from AE-200A.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Air volume
SW No.
Setting
Function No.
Setting Data
N/A
- -
30
0
(Factory setting)
N/A (Night-purge
function is not available)
- - 1 Fan speed 1
- - 2 Fan speed 2
- - 3 Fan speed 3
- - 4 Fan speed 4
No.31
Night-purge setting 2)
Outdoor and indoor temperature gap
Set one of conditions for Night-purge start, temperature gap between
indoor and outdoor.
When the actual gap between indoor and outdoor becomes bigger
than the setting, Night-purge starts.
This function is N/A from Lossnay unit DIP-SW.
When using PZ-62DR-E and AE-200A together, set all conditions
from AE-200A.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Outdoor and indoor
temperature gap
SW No.
Setting
Function No.
Setting Data
N/A
- -
31
0
0 K (0 °F/0 °C ) or more
- - 1
1 K (1.8 °F/1˚C) or more
- - 2
2 K (3.6 °F/2˚C) or more
- - 3
3 K (5.4 °F/3˚C) or more
- - 4
4 K (7.2 °F/4˚C) or more
- -
5
(Factory setting)
5 K (9 °F/5˚C) or more
- - 6
6 K (10.8 °F/6˚C) or more
- - 7
7 K (12.6 °F/7˚C) or more
No.32
Night-purge setting 3)
The lowest outdoor temperature
Set one of conditions for Night-purge start, maximum outdoor
temperature within 72 hours.
When this setting temperature is low, it is likely to start Night-purge.
This function is N/A from Lossnay unit DIP-SW.
When using PZ-62DR-E and AE-200A together, set all conditions
from AE-200A.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
The lowest outdoor
temperature
SW No.
Setting
Function No.
Setting Data
N/A
- -
32
0 59 ˚F (15 ˚C) or more
- - 1 61 ˚F (16 ˚C) or more
- -
2
(Factory setting)
63 ˚F (17 ˚C) or more
- - 3 64 ˚F (18 ˚C) or more
- - 4 66 ˚F (19 ˚C) or more
- - 5 68 ˚F (20 ˚C) or more
- - 6 70 ˚F (21 ˚C) or more
- - 7 72 ˚F (22 ˚C) or more
- - 8 73 ˚F (23 ˚C) or more
- - 9 75 ˚F (24 ˚C) or more
- - 10 77 ˚F (25 ˚C) or more
- - 11 79 ˚F (26 ˚C) or more
- - 12 81 ˚F (27 ˚C) or more
- - 13 82 ˚F (28 ˚C) or more
- - 14 84 ˚F (29 ˚C) or more
- - 15 86 ˚F (30 ˚C) or more
No.33
Night purge setting 4)
Outdoor temperature detection period
Night-purge is decided to start or not by the OA temperature within X
hour.
X hour can be selected from 24, 48 or 72 hrs.
It is possible to operate Night-purge on Sunday midnight or Monday
early morning by select longer setting even Lossnay stops.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
OA temperature
detection period
SW No.
Setting
Function No.
Setting Data
N/A
- -
33
0 24 hrs
- - 1 48 hrs
- -
2
(Factory setting)
72 hrs
No.34
Input priority setting
Set to follow input to the main unit from air conditioner, fan speed
controller, etc.
When multiple Lossnay units fan speed is externally controlled via
CN17 or CN26, select individual control or bunch control.
When bunch control is selected, connect PZ-62DR-E and input
external signal to the main unit.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
PZ-62DR-E
Setting
check
Input priority setting
SW No.
Setting
Function No.
Setting Data
N/A
- -
34
0
(Factory setting)
Bunch control priority
- - 1 Individual control priority