Installation Manual
Eng-15
5. Function settings (continued)
No Function
Setting Data
Factory
setting
DIP-SW
No.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1
Filter maintenance and fan
power up setting against lter
choking
Indicator
N/A
Fan
power up
N/A
Indicator
available
Fan
power up
N/A
Indicator
available
Fan
power up
available
Indicator
N/A
Fan
power up
available
— — — — — — — — — — — — 0 —
2
Lossnay core maintenance
indicator setting
N/A
Available
— — — — — — — — — — — — — — 0 —
5
Automatic recovery setting after
power interruption
Dip-SW
priority
Stop
when the
power is
On
Start
when the
power is
On
Return to
the state
before
interrup
-
tion
— — — — — — — — — — — — 0 2-8
6
Indoor negative pressure
setting
Dip-SW
priority
N/A
Supply
1 down
Supply
2 down
— — — — — — — — — — — — 0 2-4
7 Indoor positive pressure setting
Dip-SW
priority
N/A
Exhaust
1 down
Exhaust
2 down
— — — — — — — — — — — — 0 2-5
8
Max. fan speed setting during
the rst 30 minutes
N/A
Available
— — — — — — — — — — — — — — 0 —
9
Delay start setting for air
conditioner starting
Dip-SW
priority
N/A 15 min 30 min — — — — — — — — — — — — 0 2-3
12
Monitor output setting
TM3
90
Dip-SW
priority
Operation
monitor
Malfunction
monitor
By-pass
monitor
Supply fan
monitor
Exhaust
fan monitor
Pre-
heater
output
SA fan monitor
output with
delay operation
(for After heater)
— — — — — — — — 0
5-1
5-2
13
Monitor output setting
PZ-4GS-E COM-OUT1
Operation
monitor
Malfunction
monitor
By-pass
monitor
Supply fan
monitor
Exhaust
fan monitor
Pre-
heater
output
SA fan monitor
output with
delay operation
(for After heater)
— — — — — — — — — 1 —
14
Monitor output setting
PZ-4GS-E COM-OUT2
Operation
monitor
Malfunction
monitor
By-pass
monitor
Supply fan
monitor
Exhaust
fan monitor
Pre-
heater
output
SA fan monitor
output with
delay operation
(for After heater)
— — — — — — — — — 2 —
15
Monitor output setting
PZ-4GS-E COM-OUT3
Operation
monitor
Malfunction
monitor
By-pass
monitor
Supply fan
monitor
Exhaust
fan monitor
Pre-
heater
output
SA fan monitor
output with
delay operation
(for After heater)
— — — — — — — — — 3 —
16
Monitor output setting
PZ-4GS-E COM-OUT4
Operation
monitor
Malfunction
monitor
By-pass
monitor
Supply fan
monitor
Exhaust
fan monitor
Pre-
heater
output
SA fan monitor
output with
delay operation
(for After heater)
— — — — — — — — — 4 —
17
Exhaust fan setting during air
conditioner defrosting
No
change
Stop
Dip-SW
priority
— — — — — — — — — — — — — 2 5-3
18
Exhaust fan setting at OA
temperature lower than 5˚F
(-15 ˚C)
No
change
Forced to
fan speed
2 or less
— — — — — — — — — — — — — — 0 —
19 Interlock mode setting
ON/OFF
interlock
ON
interlock
OFF
interlock
External
input giv
-
en priority
— — — — — — — — — — — — 0 —
28 Pulse input setting
Dip-SW
priority
Non-pulse
input
Pulse
input
— — — — — — — — — — — — — 0 2-2
30
Night-purge setting 1)
Air volume
N/A
Fan speed 1 Fan speed 2 Fan speed 3 Fan speed 4
— — — — — — — — — — — 0 —
31
Night-purge setting 2)
Outdoor and indoor
temperature gap
0 K
(0˚F)
1 K
(1.8˚F)
2 K
(3.6˚F)
3 K
(5.4˚F)
4 K
(7.2˚F)
5 K
(9˚F)
6 K
(10.8˚F)
7 K
(12.6˚F)
— — — — — — — — 5 —
32
Night-purge setting 3)
The lowest outdoor
temperature
Setting Data 0 to 15 --
>
The lowest outdoor temperature for Night-purge 59˚F (15˚C) to 86˚F (30˚C) 2 —
33
Night-purge setting 4)
Outdoor temperature detection
period
24 hrs 48 hrs 72 hrs — — — — — — — — — — — — — 2 —
34 Input priority setting
Bunch
control
priority
Individual
control
priority
— — — — — — — — — — — — — — 0 —
36
Outdoor temperature display
setting
N/A
Available
— — — — — — — — — — — — — — 1 —
37
Indoor temperature display
setting
N/A
Available
— — — — — — — — — — — — — — 1 —
38
CO
2
concentration display
setting
N/A
Available
— — — — — — — — — — — — — — 1 —
39
Calculated supply air
temperature display setting
N/A
Available
— — — — — — — — — — — — — — 0 —
40
Temperature exchange
eciency setting (10 digit)
Setting Data 0 to 9 --
>
10 digit of temperature exchange eciency 0 to 9 — — — — — — 7 —
41
Temperature exchange
eciency setting (1 digit)
Setting Data 0 to 9 --
>
1 digit of temperature exchange eciency 0 to 9 — — — — — — 0 —
42
Outdoor temperature
correction
Setting Data 0 to 14 --
>
Outdoor temperature correction -7 K (-12.6˚F) to 7 K (12.6˚F) — 7 —
43 Indoor temperature correction Setting Data 0 to 14 --
>
Room temperature correction -7 K (-12.6˚F) to 7 K (12.6˚F) — 7 —
44 CO
2
concentration correction
Setting Data 0 to 10 --
>
CO
2
concentration correction -500ppm
〜
500ppm
(100ppm in increments)
— — — — — 5 —
45 Supply fan monitor threshold
Fan speed
1 or higher
Fan speed
2 or higher
Fan speed
3 or higher
Fan speed
4
— — — — — — — — — — — — 0 —
46 Exhaust fan monitor threshold
Fan speed
1 or higher
Fan speed
2 or higher
Fan speed
3 or higher
Fan speed
4
— — — — — — — — — — — — 0 —