DP V1/V2 Slave Parameters
To access the DP V1/V2 slave parameters open the
Slave Parameter Settings
menu and click
on the
DP V1/V2 Slave Parameters
button.
The parameters have the following meaning:
Item Description
DP V1 support enabled
Enable supported alarm types.
Watchdog time base 1 ms
The slave interprets the given value for watchdog time
as a multiple of 1 ms instead of 10 ms.
'Fail Safe' function enabled
The slave works in 'Fail Safe' mode.
Slave-specific check of
cfg_data
The slave applies a slave specific check to the
configuration data sent by the master.
Update Alarm
The slave can send Update alarms.
Status Alarm
The slave can send Status alarms.
Manufacturer Specific Alarm
The slave can send Manufacturer Specific alarms.
Diagnostic Alarm
The slave can send Diagnostic alarms.
Process Alarm
The slave can send Process alarms.
Pull/Plug Alarm
The slave can send Pull/Plug alarms.
Allow max. one alarm of
each type
Only one alarm of each type can be sent.
Note:
If the watchdog time has been set for all slaves via the master parameter settings, the
option for setting the WDT time base to 1 ms is disabled.
Extended User Parameters
To access the extended user parameters from the graphical network editor, click on the User
Param. button in the
Slave Parameter Settings
dialog.
User parameters for the slave device can be defined individually. The purpose of user parameters
is to parameterize the individual slave. For example the slave can be an analog input device and
the operating mode of the input channel must be parameterized at startup of PROFIBUS.