Parameter Description
Baudrate Transfer rate (must be supported by all slaves)
T_sl Slot time (max interval to wait for response)
min T_sdr min station delay of responder
max T_sdr max station delay of responder
T_qui Quiet time
T_set Setup time
T_tr Target rotation time
GAP factor controls the GAP update timer
HSA highest station address
Max retry limit max. number of retries
When pressing the <Default> button all values are set to their default values for the currently
selected baud rate.
Note:
If you change the baud rate of an existing PROFIBUS DP network, power off the slaves.
Otherwise the slaves cannot synchronize with the newly defined baud rate.
The inputs are checked against the input limits when leaving the dialog with the <OK> button.
Additionally the following consistency checks are performed:
·
min T_sdr < max T_sdr
·
T_qui < min T_sdr
·
max T_sdr < T_sl
·
T_sl < T_tr
Note:
If you are not an experienced PROFIBUS network administrator the bus parameters
should not be changed except in the following cases:
·
more than 15 slave stations are connected (target rotation time has to be calculated
again)
·
the network consists of more than 1 master (target rotation time has to be calculated
again)
For the correct parameter setting of the target rotation time TTR (t_tr) please refer to the
PROFIBUS standard. However, it is important that the target rotation time is large enough to
enable the master module to poll each connected slave once per token cycle.
Insert DP Slave
In the graphical network editor right-click on the PROFIBUS line to open the context menu. Select
'Insert DP-Slave' to access the
GSD Device Database
. After having selected a Slave Device
Group, a list of all slave models assigned to the respective group is displayed. For the selected
slave the vendor and revision string, the bitmap and the path of the GSD file and the bitmap file
are displayed.