Specifications

48How to Create a New DP Master Project
(c) 2006 MITSUBISHI ELECTRIC CORPORATION
The field ‘
Estimated bus cycle time
shows the expected minimum interval between two I/O data
exchanges with a slave. The cycle time depends mostly on the following factors:
·
baud rate
·
number of slaves configured in the master
·
I/O size of the configured slaves
·
max response time of each slave (max Tsdr)
·
number of acyclic requests, diagnostic telegrams and retries
·
other master stations sharing the same PROFIBUS network
Note:
The cycle time must be observed when setting the minimum slave interval and the
watchdog time. If the actual cycle time exceeds the settings for these parameters, the
communication cannot be started.
When using the estimated cycle time for adjusting min. slave interval and watchdog time
add sufficient time for communication of other masters and for acyclic data exchange
(DPV1 and diagnostic messages).
Communications Parameters of Master Settings
Parameter Meaning
Name
Shows the project specific name of the master
Baudrate
Transfer rate for the communication. Define a baudrate, which is
supported by all slaves.
FDL address
FDL address (station number)
Starting I/O
number
Module head address on the base unit
Note: the starting I/O number is only necessary for 'Copy POU' and 'I/O
Mapping POU'. It is not required for the download of the PROFIBUS
configuration. For online access the module is identified by the slot number
in the transfer setup.