Specifications

38Main Menu
(c) 2006 MITSUBISHI ELECTRIC CORPORATION
Download to project module type only
GXDP will allow a download only to the same module type as specified in the project. If the
module found in the specified slot of the target PLC rack does not match that of the project, an
error message is displayed.
If the user wants to download the project to a different module type, the project must first be
converted to the type of the connected module. This is done by selecting the
Change Master
Type
menu item.
For QnPRH redundant systems
If the connected PLC is a QnPRH, GXDP automatically checks whether both PLCs of the
redundant system are accessible by using the tracking cable and also checks the current backup
mode. The procedure for download is adapted according to the result of these tests
1. Backup’ mode and both PLCs connected: the user is asked for confirmation to update both
master modules. If the user confirms, the system is automatically switched to ‘Separate’
mode and default device tracking is turned off. Then the configuration is downloaded to the
master in the control as well as in the standby system. After the download, the system is set
back to the original state.
2. ‘Separate’ mode and both PLCs connected: the user is asked, whether the configuration of
both master modules or only of the one in the locally connected PLC should be updated. In
both cases device tracking is turned off, while the configuration is downloaded to the
master(s). After the download, device tracking is enabled again.
3. Debug mode or only one PLC connected: only the master in the connected PLC is
updated.
AutoRefresh Update
If the user has selected 'AutoRefresh (Update of CPU)' or 'AutoRefresh (Update of GID Project)' in
the 'PLC and GID Settings' dialog, the autorefresh settings are updated, after the configuration