Specifications
36Main Menu
(c) 2006 MITSUBISHI ELECTRIC CORPORATION
To apply the updated GSD database to an existing project the option
GSD database has priority
must be enabled.
GSD database has priority
This option controls, whether GSD information in the project file, if present, is overwritten by the
corresponding information from the GSD database for the same types.
This option has the following effects:
When opening a project file
·
Case 1: The option GSD database has priority is selected
GX Configurator-DP tries to locate the GSD information for the slave types, which are
used in the project, in the local GSD database. If the type cannot be found in the
database, it tries to find the information in the project file. If that fails as well, an error
message is displayed and the project cannot be opened.
·
Case 2: The option GSD database has priority is not selected
GX Configurator-DP tries to locate the GSD information for the slave types, which are
used in the project, in the project file itself. If the type cannot be found in the project, it
tries to find the information in the local GSD database. If that fails as well, an error
message is displayed and the project cannot be opened.
When saving a project file
When a project is saved, GXDP adds the GSD information for all slave types, which are used in
the project and for which the GSD information does not already exist in the project file, to the
project file. GSD information in the project file for types, which no longer are used in the project, is
removed from the project file. GSD information existing in the project file for types still in use, is
handled depending on the option 'GSD database has priority'.
·
Case 1: The option 'GSD database has priority' is selected
If the GSD information for a certain type exists in both project file and local GSD
database, the GSD entries in the project file are deleted and replaced by those from the
GSD database.
·
Case 2: The option 'GSD database has priority' is not selected
Existing GSD entries in the project file for types, which are still in use, will not be
changed.
5.3 Online Menu
The Online menu offers the following commands:
Command Description
Transfer Setup
defining the network connection type (PC to PLC).
Transfer
downloading the configuration from the current project to
the module specified by the current transfer setup.
Start/Stop
PROFIBUS
user can start and stop the cyclic DP data transfer.
Command Transfer Setup
The dialog is started via the menu item
Online/Transfer Setup
. When a new project is created, a