Specifications
33 GX Configurator-DP
(c) 2006 MITSUBISHI ELECTRIC CORPORATION
Input Fields Description
Slave Specific
Transfer
Buffer devices are assigned to each slave individually in the
column "Buffer MIT-Address" in the "I/O Mapping" dialog.
This option is only useful in combination with autorefresh or
for the 'Copy POU' of the FX3U-64DP-M master.
Block Transfer
The input as well as the output areas of all slaves are
transferred in a single step using one common transfer
buffer.
Input: device address, where the slave input data is copied
to from the buffer memory.
Output: device address, where the slave output data is
copied from to the buffer memory.
Comm. Trouble Area
Device address, where the so-called ‚Communication
Trouble Area’ is copied to from the buffer memory
Extd. Comm. Trouble
Area
Device address, where the so-called ‚Extd. Communication
Trouble Area’ is copied to from the buffer memory
Slave Status Area
Device address, where the so-called ‚Slave Status Area’ is
copied to from the buffer memory
Data Transfer using...
Select, whether TO/FROM instructions or autorefresh is
used for exchanging the data between PLC device memory
and the buffer memory of the master module
Copy Instructions
Use TO/FROM instructions (for all PLC series except
Q-series 'Remote I/O')
AutoRefresh (Update
of CPU)
Use autorefresh and update of the settings online on the
CPU (Q-series only except 'Remote I/O')