Specifications
3PROFINET Controller ME1PN1FW-Q
(c) 2013 MITSUBISHI ELECTRIC CORPORATION
No.
Name
Description
Channel 1
4
10BASE-T/100BASE-TX
interface connector (RJ45)
Channel 2
Not used for the PROFINET Controller
5
Serial number plate
Hardware serial number
6
EJECT button
Press to eject CF card from slot
7
CompactFlash (CF) card
installation slot
Slot for installing CF card
8
RUN/STOP/MODE switch
Sets the operation mode
9
RESET/SELECT switch
Used to reset the module
10
USB interface connector
For USB connections
Not supported by the PROFINET Controller. The module
can only be accessed via the first Ethernet port.
11
Battery
Buffers data in RAM
12
Battery connector pin
Pin to connect battery
Note: when delivered the battery is not connected to en-
sure its capacity.
13
RS-232 interface connec-
tor
For RS-232 connections
Not supported by the PROFINET Controller.
Technical Data
Maximum number of total cyclic
input data (1)
9228 bytes
Maximum number of total cyclic
output data (1)
9900 bytes
Maximum number of cyclic input
data
1437 bytes per device (= IOCR data length)
Maximum number of cyclic out-
put data
1437 bytes per device (= IOCR data length)
Maximum number of configured
devices
128
Minimum cycle time
1 ms