Specifications
55PROFINET Controller ME1PN1FW-Q
(c) 2013 MITSUBISHI ELECTRIC CORPORATION
RUN
STOP
PROFINET stack is in STOP.
Output data = old values and IOPS and IOCS set to BAD
Input data are updated in the high speed area
STOP
RUN
PROFINET stack is in RUN.
Output data = old values an IOPS and IOCS set to GOOD
Input data are updated in the high speed area
STOP
STOP
PROFINET stack is in STOP.
Output data = old values an IOPS and IOCS set to BAD
Input data are updated in the high speed area
2.2 LED Display
2.2.1 User LED
The 'USER' LED is the bottom-right one in the six LEDs group on the front of the ME1PN1FW-Q.
This LED signals PROFINET Controller specific states in combination with the 7-segment LED dis-
play. For the meaning of the other LEDs please consult the user manual of the Q12DCCPU-V.
State
Meaning
RED
Error, see 7 segments LED
RED slow blink
Some IO-devices are not connected.
RED rapid Blink
Network storm
Green
All OK. All IO-devices connected whatever their mode (manual or auto-
matic)
Green slow blink
All OK. All IO-devices in automatic mode are connected. All IO devi-
ces in manual mode are not connected.
Green rapid Blink
All OK. All IO-devices in automatic mode are connected. Some IO de-
vices in manual mode are connected, some are not connected
Orange
All IO-devices connected whatever their mode (manual or automatic).
However, some configuration mismatches exist.