Device Advanced Status (IOD_ADV_STS Registers)
For each IO-device a byte in the variable 'vPN_ACYCLIC_DIAG_INPUTS.IOD_ADV_STS' contains
the detailed status error code, when the corresponding bit in IOD_ERR_STS is set. Each element in
the word array 'IOD_ADV_STS' contains the status codes of two devices, the status of the device
with an odd index is placed in the low byte, the status of the device with an even index is placed in
the high byte.
IOD_CONN_STS,
IOD_ERR_STS
Byte Value in
IOD_ADV_STS
Comment
N/A
0
IO-device Status is not set. (no error)
1,1
1
The IO-device produces in stop mode
1,1
2
One of IOPS in input frame is in bad.
1,1
3
One of IOCS in input frame is in bad.
1,1
4
IO-device Configuration does not match.
1,1
5..99
Reserved
0,1
100
No answer from the IO-device at the DCP identify
request. The configured name is not present on
the network.
0,1
101
Duplicate name for the IO-device. The DCP identify
request received several answers from different IO-
devices.
0,1
102
Duplicate IP address detected during DCP identify
request.
0,1
103
Out of AR resource. The device is already connec-
ted and do not accept more connection.
0,1
103-252
Reserved, to be completed during development.
0,1
253
Connection failed.
0,0
254
Never connected. This IO-device ID is present in
the configuration, but the PROFINET stack never
sent a connect request.
0,0
255
Not used. This IO-device ID is not present in the
configuration.
Diagnostic Area (ADV_DIAG_* Registers)
In the ADV_DIAG_* registers the PROFINET stack can report some advanced information on the
PROFINET Controller state (used for technical support only).