51PROFINET Controller ME1PN1FW-Q
(c) 2013 MITSUBISHI ELECTRIC CORPORATION
PROFINET IO-Controller to CPU
Global Variable Identifier
IO-Device
Number
Values
0
1
vPN_MGMT_INPUTS.IOD_CONN_STS[116]
…
vPN_MGMT_INPUTS.IOD_CONN_STS[127]
116
..
127
IOD_ERR_STS Registers
The following 128 bits indicate for each IO-device, whether an error has occurred.
PROFINET IO-Controller to CPU
Global Variable Identifier
IO-Device
number
Values
0
1
vPN_MGMT_INPUTS.IOD_ERR_STS[0]
…
vPN_MGMT_INPUTS.IOD_ERR_STS[15]
0
..
15
No Error
Error
vPN_MGMT_INPUTS.IOD_ERR_STS[16]
…
vPN_MGMT_INPUTS.IOD_ERR_STS[31]
16
..
31
…
…
vPN_MGMT_INPUTS.IOD_ERR_STS[116]
…
vPN_MGMT_INPUTS.IOD_ERR_STS[127]
116
..
127
For each IO-device the following combinations are possible:
IOD_CONN_STS
IOD_ERR_STS
Meaning
0
0
IO-device not connected because no connection re-
quested.
1
0
IO-device connected, connection without error.
0
1
IO-device not connected.
In automatic mode connection not possible.
In manual, last connection request failed.
1
1
IO-device connected but connection in error