Specifications

31PROFINET Controller ME1PN1FW-Q
(c) 2013 MITSUBISHI ELECTRIC CORPORATION
Possible Values for Status
Value
Comment
0
Status OK, function
1
Profinet stack not started
2
No ethernet link
3
No IO-Device detected
4
Reception buffer too small (internal stack error)
6
Device not connected
7
Device not configured
8
Profinet error
Record Block Explicit Write (connected)
Request format
Word
Offset
ID
Value
0
RequestID
PLC value
1
2
ServiceID
4
3
Status
0x55
4
DeviceID
Requested device
5
6
API
API number used to perform the write
7
8
SlotNumber
Slot number targeted
9
SubslotNumber
Subslot number targeted
10
Index
Index of the record block
11
Data length
(byte)
data size
12
PnDeviceID
0
13
PnVendorID
0