Specifications
212 GX Configurator-PN
(c) 2013 MITSUBISHI ELECTRIC CORPORATION
9
Appendix
9.1 Troubleshooting
9.1.1 Factory Default Settings
Problem
The ME1PN1FW-Q cannot be accessed from GX Configurator-PN, although network address set-
tings and cabling are correct.
Solution
To reset the ME1PN1FW-Q to its factory default settings execute the following operations.
Important: the ME1PN1FW-Q must be placed alone in the first slot (marked 'CPU') of the PLC
backplane and the CF card must be removed from its card reader slot! ).
Note: the position of the LEDs and the switches is indicated in the section 'PROFINET Controller
ME1PN1FW-Q'.
1. set the MODE/STOP/RUN switch on the front to the MODE position
2. reset the module by setting the RESET/SELECT switch to the RESET position and then back to
the middle position or power-cycle the CPU
3. confirm that the mode LED shows an orange light and the 7-segment LED displays '00'
4. set the MODE/STOP/RUN switch to the STOP position
5. set the RESET/SELECT switch to the SELECT position multiple times, until the 7-segment dis-
play displays '11'
6. set the MODE/STOP/RUN switch to the RUN position
7. confirm that the green RUN LED is flashing first and then turns off with the 7-segment LED dis-
playing '00'
8. set the MODE/STOP/RUN switch to the STOP position
9. reset the module by setting the RESET/SELECT switch to the RESET position and then back to
the middle position
10. confirm that the MODE LED shows a steady green light and both RUN and USER LEDs show
a flashing green light