Specifications

198 GX Configurator-PN
(c) 2013 MITSUBISHI ELECTRIC CORPORATION
Value (hex)
ID
0x0011
Network component problem notification
0x0012
Time data changed notification
0x0013
Dynamic Frame Packing problem notification
0x0014
MRPD problem notification
0x0015
System Redundancy
0x0016 - 0x001D
Reserved
0x001E
Upload and retrieval notification
0x001F
Pull module
0x0020 - 0x007F
Manufacturer specific
0x0080 - 0x00FF
Reserved for profiles
0x0100 - 0xFFFF
Reserved
Alarm Specifier
Bits
Description
Value
0 - 10
Sequence number
0 to 2,047, incremented upon each indication
11
Diagnosis channel
0x00: No diagnosis available
0x01: Diagnosis available
12
Specific diagnosis
0x00: No diagnosis available
0x01: Diagnosis available
13
Diagnosis sub-module
0x00: No diagnosis available
0x01: Diagnosis available
14
Reserved
0x00
15
AR diagnosis
0x00: No diagnosis available
0x01: Diagnosis available
Alarm Management
By default the PROFINET stack can handle alarms automatically without reporting any indication to
the PLC program. The PLC program can overwrite this default setting per device in order to manage
alarms for a device by itself. To select 'manual handling' for alarms of a specific device a bit, which
corresponds to the device, must be set in the global variable 'vPN_MGMT_OUTPUTS', which con-
tains the PROFINET management output structure.