Specifications
197PLC Code for PROFINET Controller
(c) 2013 MITSUBISHI ELECTRIC CORPORATION
Word Offset
ID
Value
4
Slot number
Slot number of the alarm
5
SubSlot number
Subslot number of the alarm
6
Specifier
Alarm specifier
7
Module ident number
Module ID of the Alarm
8
9
SubModule ident number
Submodule ID of the Alarm
10
11
Data length
Data Size in byte
12 + Data length / 2 - 1
Data
0 to 1432 bytes
Alarm Types
Value (hex)
ID
0x0000
Reserved
0x0001
Diagnosis
0x0002
Process
0x0003
Pull
0x0004
Plug
0x0005
Status
0x0006
Update
0x0007
Media Redundancy
0x0008
Controlled by supervisor. Logical “Pull” of a submodule to withdraw owner-
ship
0x0009
Released. Logical “Plug” of a submodule to return ownership or trigger a re-
parameterization
0x000A
Plug Wrong Submodule
0x000B
Return of Submodule
0x000C
Diagnosis disappears
0x000D
Multicast communication mismatch notification
0x000E
Port data change notification
0x000F
Sync data changed notification
0x0010
Isochronous mode problem notification