Specifications
184 GX Configurator-PN
(c) 2013 MITSUBISHI ELECTRIC CORPORATION
7.10.3 'PROFINET Controller Status' Dialog
This dialog displays the current status of the PROFINET controller and provides means to start/stop
the data exchange in the PROFINET network. It retrieves the multi-CPU settings including the buffer
device addresses online from the CPUs independently of the current GX Configurator-PN configurati-
on. Only the IP address of the PN controller and the transfer setup for the QnU-CPU are taken from
the current project.
Name
Description
Choices / Range
Default
PROFINET Con-
troller Status
current status of the PN controller (see
list below)
-
-
Additional Status
Information
additional information for specific status
codes
-
-
Start PROFINET
or
Stop PROFINET
starts respectively stops the cyclic data
exchange by the PN controller
text depends on the state of the
IOC_STS_STARTED flag
button is only enab-
led, if the PN ctrl
has the flag
‘IOC_STS_CONFIG
_OK’ set, otherwise
the button is disab-
led
-
Buffer Devices
displays the currently configured devices
for the PROFINET refresh buffers
-
-
Close
close dialog and proceed
-
Default
button
To obtain the currently active device addresses the dialog first reads the start I/O number of the con-
trolling QnU-CPU from the PN controller. It then reads the multi-CPU settings including buffer devi-
ces from that QnU-CPU, independent of the settings in the current GX Configurator-PN project. The-
se active device addresses are displayed in the status dialog.