Specifications

133User Interface
(c) 2013 MITSUBISHI ELECTRIC CORPORATION
Name
Description
Choices /
Range
Default
Comments
Free text related to a device. The total number of
characters must not exceed 80.
0 - 80 cha-
racters
Addressing Mo-
de
Defines the way of obtaining the IP configuration
which may be DCP, Local or DHCP. The modes
vary according to the contents of the GSD for
the IO-Device.
DCP: during the connection, the IO-Controller
sets the IP address of the IO-Device.
DHCP: during the connection, the IO-Controller
compares the IP address of the IO-Device with
that configured. If they are identical, the connec-
tion can go ahead. If not, the connection fails.
Local: during the connection, the IO-Controller
uses the configured IP address.
IP Address
This IP address will be the IP address of the IO-
Device after connection if the selected addres-
sing is DCP.
This IP address shall be the same as the IP ad-
dress configured inside the IO-Device if the se-
lected addressing mode is different than DCP.
Device Name
This field shall be the same as name configured
inside the IO-Device. (See Name an IO-Device)
Description
Provides help on the selected field.
read-only
-
Previous
Get settings of previous I/O device (slave)
disabled for
first device
-
Next
Get settings of next I/O device (slave)
disabled for
last device
-
OK
Close dialog and save changes
-
Default
button
Cancel
Close dialog and discard changes
-
-
Help
Open online help
-
-
Note: when creating a configuration from the ‘Network Detection View’ (aka ‘automatic configuration
mode), IP address and name of the device are already set. When manually adding the device, these
items must be entered by the user.