User`s manual

8
Number Name Description
5) Indicator LEDs Data link status can be conformed by the on/off statuses of
the LEDs.
6) Connector Connector for connection to the GOT
7) Module fixing screws Screws for installation to the GOT (M3 3 screw)
8) Terminal block
Terminal block for cable connection (M3 8 screw)
9) Rating plate -
10) Mounting screw Mounting screw to be fixed with the GOT main unit
11) Interface connector Connector connecting to GOT
12) Extension connector Connector connecting with A8GT-J61BT13
LED
Name
Description
RUN
LED
On : Indicates that the module is normal.
Off : Indicates a watchdog timer error.
L RUN
LED
On : Indicates that communication is normal.
Off : Indicates a communication break
(time excess error).
SD LED On : Indicates data transmission.
RD LED On : Indicates data receive.
L ERR.
LED
On : Indicates a communication data error
(CRC error).
Flicker : Indicates that any switch (1 to 4) position
was changed while power is on.
Off : Indicates that communication is normal.