User`s manual
7
Number Name Description
1) Mode setting switch Used to set the operating status of the module.
(Factory setting:0)
2) Station number
setting switches
Used to set the station number of the A8GT-J61BT13
between 1 and 64. (Factory setting: 01)
Use " 10" to set the tens.
Use " 1" to set the units.
3) Transmission
baudrate setting
switch
Used to set the transmission speed of the module.
(Factory setting:0)
4) Condition setting
switches
Used to set the operational conditions. (Factory setting:OFF)
Number Name Description
0Online
Data link enabled and automatic
return made
1(Reserved) -
2 Offline Disconnected from data link
3 to F (Reserved) -
Number
to be Set
Transmission Baudrate
0 156kbps
1 625kbps
22.5Mbps
3 5Mbps
4 10Mbps
5 to 9
Reserved (If the value you set is 5 to 9, the
L.ERR LED is lit to indicate a communication
error.)
Number Setting Item
Switch Position
ON OFF
SW1
Input data status of faulty
data link station
Held Cleared
SW2
Number of occupied
stations
4 stations 1 station