User`s manual

2
2. Performance Specifications
The following is the performance specification of CC-Link communication unit.
For the general specifications of CC-Link communication unit, refer to the GT15
User’s Manual.
*1
Item Specifications
CC-Link station type Intelligent device station
Number of link occupied stations May be selected between 1 and 4.
Maximum number of link points
per system
Remote I/O (RX,RY)
*2
2048 points
Remote register (RWw) 256 points
Remote register (RWr) 256 points
Number of link points per station
Remote I/O (RX,RY)
*2
32 points
Remote register (RWw) 4 points
Remote register (RWr) 4 points
Number of
link points
per number
of occupied
stations
1 station occupied
Remote I/O (RX,RY)
*2
32 points
Remote register (RWw) 4 points
Remote register (RWr) 4 points
4 stations occupied
Remote I/O (RX,RY)
*2
128 points
Remote register (RWw) 16 points
Remote register (RWr) 16 points
Transmission speed 156kbps/625kbps/2.5Mbps/5Mbps/10Mbps
Max. transmission distance Depends on the transmission speed.
Max. number of modules
connected
26
The max. number of modules connected depends on the
configuration of the CC-Link system to be used.
For more details on the max. number of modules
connected, refer to the CC-Link System Master-Local
Module User’s Manual.
Connection cable CC-Link dedicated cable
Terminal block 8-pin terminal block (M3 8 screws)
Applicable crimping terminal RAV1.25-3, RAV2-3.5
(conforming to JIS C2805)
Internal current consumption
(DC5V)
0.27A in total with GT15-75IF900
Weight 0.36kg (0.79lb) in total with GT15-75IF900