User`s manual

2
*1 : Please note that use of a fiber-optic cable requires the expertise,
special tools and dedicated connector for connection. Please
contact your local Mitsubishi Electric System & Service Co., Ltd. or
representative, for the purchase of the required items.
Max. number of
networks
239
Max. number of groups 32
Transmission path Duplex loop
Optical fiber
specifications
1000BASE-SX(MMF) fiber-optic cable
Standard IEC60793-2-10 Types A1a.1 (50/125 m multimode)
Transmission
loss (max.)
3.5 (dB/km) or less ( = 850nm)
Transmission
band (min.)
500 (MHz
km) or more ( = 850nm)
Connector specifications Duplex LC connector
Standard IEC61754-20: Type LC connector
Connection
loss
0.3 (dB) or less
Polished
surface
PC (Physical Contact) polishing
Internal current
consumption
1.07A
Weight 0.28kg (0.62lb)
Item Specification