User`s manual

1
1. Overview
This manual explains the CC-Link IE controller network communication unit
(hereinafter referred to as CC-Link IE communication unit).
The CC-Link IE communication unit allows the GOT1000 series to function as a
normal station on the CC-Link IE controller network.
Refer to GT15 User's Manual for GOT to which this unit can be installed.
2. Specifications
The performance specifications of the CC-Link IE communication unit are
indicated below.
The general specifications of the CC-Link IE communication unit are the same as
those of the GOT.
For the general specifications of the GOT, refer to GT15 User's Manual.
When using the CC-Link IE controller network connection, make the
communication setting to perform communication with programmable
controllers.
For details of the CC-Link IE controller network connection, refer to GOT1000
Series Connection Manual.
Item Specification
Max. link points
per network
LB 32K points (32768 points, 4KB)
LW 128K points (131072 points, 256KB)
LX 8K points (8192 points, 1KB)
LY 8K points (8192 points, 1KB)
Max. link points
per station
LB 16K points (16384 points, 2KB)
LW 16K points (16384 points, 32KB)
LX 8K points (8192 points, 1KB)
LY 8K points (8192 points, 1KB)
Transient transmission
capacity
Up to 1920 bytes
Communication speed 1Gbps
Communication method Token ring
Number of stations per
network
Up to 120 stations
(Control station: 1, Normal station: 119)
*1
Connection cable
Fiber-optic cable (Multi-mode fiber)
( CC-Link IE Controller Network Reference Manual)
Overall cable distance 66000m (When 120 stations are connected)
Station-to-station
distance (Max.)
550m (Core/Clad = 50/125 ( m))