Specifications
20
Split System Inverter Air Conditioners 2014
4-way ceiling cassette
RCN-TC-24W-ERRC-E5RC-EX1A
Wireless
Wired
RCH-E3
Remote control (Option)
FDTC50VF
Remote control (Option)
Wired
Wireless
RC-EX1A RC-E5 RCH-E3 RCN-T-36W-E
Wireless
RC-E5
Wired
RCH-E3
RC-EX1A
RCN-T-36W-E
Remote control (Option)
FDT60 ~ 140VF
Manufacturers Speci cations: All spec cation tables are at nominal conditions. Refer to manufacturers technical manuals.
FDT-VF.
Reverse Cycle Inverter Cassette.
FDT
Set FDT60ZMXAVF FDT71VNXVF1 FDT100VNVF1 FDT125VNXVF FDT140VNXVF
Indoor FDT60VF FDT71VF1 FDT100VF1 FDT125VF FDT140VF
Outdoor SRC60ZMXA-S FDC71VNX FDC100VN FDC125VNX FDC140VNX
Power supply Indoor Unit 1 Phase 220-240V 50Hz
Capacity
Cooling T1
kW
5.6 (1.1-6.3) 7.1 (3.2-8.0) 10.0 (4.0-11.2) 12.5 (5.0-14.0) 14.0 (5.0-16.0)
Heating H1 6.7 (0.6-7.1) 8.0 (3.6-9.0) 11.2 (4.0-12.5) 14.0 (4.0-17.0) 16.0 (4.0-18.0)
Heating H2 5.29 7.2 N/A 15.6 13.8
Input
Cooling T1
kW
1.52 2.04 2.76 3.28 4.19
Heating H1 1.70 1.94 2.74 3.43 4.2
EER Cooling T1 3.68 3.48 3.62 3.81 3.34
COP Heating H1 3.94 4.12 4.09 4.08 3.81
Sound pressure level
(JIS C9612)
Indoor
dB(A)
P-Hi:46 Hi:33
Me:31 Lo:30
P-Hi:46 Hi:35
Me:33 Lo:31
P-Hi:51 Hi:40
Me:37 Lo:35
P-Hi:51 Hi:42
Me:40 Lo:37
P-Hi:51 Hi:43
Me:41 Lo:38
Outdoor 54 51 49 50 52
Sound power level
(JIS C9612)
Outdoor dB(A) 65 66 70 72
Air ow Indoor l/s
P-Hi: 466 Hi: 300
Me: 266 Lo: 233
P-Hi: 466 Hi: 350
Me: 316 Lo: 283
P-Hi: 616 Hi: 450
Me: 400 Lo: 333
P-Hi: 616 Hi: 500
Me: 450 Lo: 383
P-Hi: 616 Hi: 500
Me: 450 Lo: 383
Panel mm T-PSA-3BW-E (35x950x950)
External dimensions
(HXWXD)
Indoor
mm
246x840x840 298x840x840
Outdoor 640x800(+71)x290 750x880(+88)x340 845x970x370 1300x970x370
Net weight
Indoor
kg
Unit 24 Panel 5.5 Unit 27 Panel 5.5
Outdoor 45 60 81 105
Refrigerant piping
Liquid line
mm
Ø6.35 Ø9.52
Gas line Ø12.7 Ø15.88
Connection method Flare connection
Refrigerant R410A
Quantity kg 1.5 2.95 3.8 4.5
Pre charged to pipe
length
m 15 30
Maximum pipe length m 30 50 100
Controller RC-EX1A Options RC-E5 or RCN-T-36W-E