(q) Refrigeration cycle system protection
1) Starting conditions
Heating
1) Operating conditions:
2) Detail of operation:
3) Reset conditions:
a)
b)
a)
b)
(model 50 : 0ºC)
(model 50 : 2ºC)
When 5 minutes have elapsed after the compressor ON or the completion of the defrost control
Other than the defrost control
2) Contents of control
a)
3) Resetting condition
When the compressor has been turned OFF
b)
When the conditions of 1) above are met, the compressor stops.
Error stop occurs when the compressor has stopped 3 times within 60 minutes.
c)
When, after meeting the conditions of a) and b) above, the compressor speed, indoor air temperature (Th1) and indoor
heat exchanger temperature (Th2) have met the conditions in the following table for 5 minutes:
Compressor speed (N)Operation mode
Cooling
Heating
Indoor air temperature (Th1)
Th1−4<Th2
Indoor air temperature (Th1)/
Indoor heat exchanger temperature (Th2)
Th2<Th1+6
50 N
<
=
10 Th1 40
<
=
<
=
0 Th1 40
<
=
<
=