Specifications

-
245
-
'10 • SR-T-091
E58
Current safe stop
1. Applicable model
5. Troubleshooting
All models
When the current safe control
has operated at the compressor
speed of 30 rps or under:
Same as above
• Excessive refrigerant amount
• Indoor,outdoor unit installation
spaces
• Faulty compressor
• Defective outdor air temp.
sensor
• Defective outdoor PCB
Diagnosis Countermeasure
2. Error detection method
3.
Condition of Error displayed
4. Presumable cause
Note:
NO
NO
NO
NO
NO
YES
YES
YES
Is outdoor
ventilation condition
good ?
Inspect
outdor air temp.
sensor
Is the refrigerant
amount nomal ?
Adjust the refrigerant
amount properly.
Secure space for inlet and
outlet.
Replace compressor.
Replace sensor.
Defective outdoor
PCB¡Replace.
(Defective outdor air temp.
sensor input circuit)
Inspect
compressor
Error code
Remote controller:
LED Green Red
Content
Indoor
Keeps flashing
Stays OFF