Specifications

-
227
-
'10 • SR-T-091
E7
Return air temperature
thermistor anomaly
Keeps flashing
1 time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
NO
NO
YES
Is the
connection of return
air temperature thermistor
connector OK?
Are the
characteristics of return air
temperature thermistor
OK?
YES
15
10
5
0 10 30 40 20 50
Temperature-resistance characteristic
Temperature thermistor resistance (k)
Temperature (°C)
5k at 25°C
(Broken wire)
(Shot circuit)
Correct.
ª
Connect
connector.
Defective return air
temperature thermistor
ª
Replace.
Defective indoor control
PCB
ª
Replace.
(Defective return air
temperature thermistor
input circuit)
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected by indoor return air
temperature thermistor (Thi-A)
3.
Condition of Error displayed
When the temperature thermistor
detects -50°C or lower for
5 seconds continuously, the
compressor stops. After 3-minute
delay, the compressor starts again
automatically, but if this error
occurs again within 60 minutes
after the initial detection.
4. Presumable cause
Defective return air
temperature thermistor
connector
Defective return air
temperature thermistor
Faulty indoor control PCB
Note:
Error code
Remote controller:
LED Green Red
Indoor
Content