Specifications

-
221
-
'10 • SR-T-091
WAIT
Communication error at
initial operation (1/3)
1. Applicable model
5. Troubleshooting
All models
When the remote controller
LCD displays “
WAIT
” 2
minutes after the power on.
Diagnosis Countermeasure
Replace the
power supply fuse.
NO
YES
NO
YES
The remote controller LCD
displays “ ”
2 minutes after the power on.
Turn the breaker off once and then
back on again 3 minutes later.
Is normal condition restored?
YES
NO
NO
YES
NO
Isn’t blown
the power supply fuse (15A) on the outdoor
unit controller?
Is AC220/240V
detected at the secondary side of
outdoor PCB?
Is the
green LED of indoor unit
flashing?
Are wires
connected properly between
the indoor and the outdoor
units?
Is approx.
DC20V detected between -
on the outdoor unit terminal
block?
YES
NO
Is approx.
DC20V detected between
-
on the indoor unit terminal
block?
NO
YES
WAIT
See next page.
Defective outdoor
PCB
¡
Replace.
Defective indoor control
PCB
¡
Replace.
Replace indoor control
PCB.
Correct connection wires
between indoor and
outdoor units.
Defective outdoor
PCB
¡
Replace.
Defective connection wire
(broken wire)
Noise
Defective indoor control
PCB
¡
Replace.
2. Error detection method
3.
Condition of Error displayed
4. Presumable cause
• Blown fuse
Faulty outdoor PCB
Connection between PCB’s
Faulty indoor control PCB
Defective remote controller
Broken remote controller wire
Note: If any anomaly is detected during communication, the error code E5 is displayed. Inspection procedure is same as above. (Excluding
matters related to connection) When the power supply is reset after the occurrence of E5, the LED will display “
WAIT
if the anomaly
continues. If the breaker ON/OFF is repeated in a short period of time (within 1 minute), “
WAIT
may be displayed. In such occasion,
turn the breaker off and wait for 3 minutes.
Error code
Remote controller:
LED Green Red
Indoor
Stays OFF
Keeps flashing
Content