Specifications
-
 98 
-
 '10 • SR-T-091
CAUTION
• Use the circuit breaker with sufficient breaking capacity.
  If the breaker does not have sufficient breaking capacity, it can cause 
the unit malfunction and fire.
• Earth leakage breaker must be installed.
  If the earth leakage breaker is not installed, it can cause electric 
shocks.
• Install isolator or disconnect switch on the power supply wiring 
in accordance with the local codes and regulations.
• After maintenance, all wiring, wiring ties and the like, should be 
returned to their original state and wiring route, and the 
necessary clearance from all metal parts should be secured.
• Secure a space for installation, inspection and maintenance 
specified in the manual.
  Insufficient space can result in accident such as personal injury due to 
falling from the installation place.
• Take care when carrying the unit by hand.
  If the unit weights more than 20kg, it must be carried by two or more 
persons. Do not carry by the plastic straps, always use the carry 
handle when carrying the unit by hand. Use gloves to minimize the risk 
of cuts by the aluminum fins.
• Dispose of any packing materials correctly.
  Any remaining packing materials can cause personal injury as it 
contains nails and wood. And to avoid danger of suffocation, be sure 
to keep the plastic wrapper away from children and to dispose after 
tear it up. 
• Be sure to insulate the refrigerant pipes so as not to condense 
the ambient air moisture on them.
  Insufficient insulation can cause condensation, which can lead to 
moisture damage on the ceiling, floor, furniture and any other 
valuables.
• When perform the air conditioner operation (cooling or drying 
operation) in which ventilator is installed in the room. In this 
case, using the air conditioner in parallel with the ventilator, 
there is the possibility that drain water may backflow in 
accordance with the room lapse into the negative pressure 
status. Therefore, set up the opening port such as incorporate 
the air into the room that may appropriate to ventilation (For 
example; Open the door a little). In addition, just as above, so 
set up the opening port if the room lapse into negative 
pressure status due to register of the wind for the high rise 
apartment etc.
• Do not install the unit in the locations listed below.
  • Locations where carbon fiber, metal powder or any powder is floating.
  • Locations where any substances that can affect the unit such as 
sulphide gas, chloride gas, acid and alkaline can occur. 
  • Vehicles and ships.
  • Locations where cosmetic or special sprays are often used.
  • Locations with direct exposure of oil mist and steam such as kitchen 
and machine plant.
  • Locations where any machines which generate high frequency 
harmonics are used.
  • Locations with salty atmospheres such as coastlines. 
  • Locations with heavy snow (If installed, be sure to provide base 
flame and snow hood mentioned in the manual).
  • Locations where the unit is exposed to chimney smoke.
  • Locations at high altitude (more than 1000m high).
  • Locations with ammonic atmospheres.
  • Locations where heat radiation from other heat source can affect the 
unit.
  • Locations without good air circulation.
  • Locations with any obstacles which can prevent inlet and outlet air 
of the unit.
  • Locations where short circuit of air can occur (in case of multiple 
units installation).
  • Locations where strong air blows against the air outlet of outdoor 
unit.
  It can cause remarkable decrease in performance, corrosion and 
damage of components, malfunction and fire.
• Do not install the outdoor unit in the locations listed below.
  • Locations where discharged hot air or operating sound of the 
outdoor unit can bother neighborhood.
  • Locations where outlet air of the outdoor unit blows directly to 
plants.
  • Locations where vibration can be amplified and transmitted due to 
insufficient strength of structure.
  • Locations where vibration and operation sound generated by the 
outdoor unit can affect seriously (on the wall or at the place near bed 
room).
  • Locations where an equipment affected by high harmonics is placed 
(TV set or radio receiver is placed within 1m).
  • Locations where drainage cannot run off safely.
  It can affect surrounding environment and cause a claim.
• Do not install the unit near the location where leakage of 
combustible gases can occur.
  If leaked gases accumulate around the unit, it can cause fire.
• Do not install the unit where corrosive gas (such as sulfurous 
acid gas etc.) or combustible gas (such as thinner and 
petroleum gases) can accumulate or collect, or where volatile 
combustible substances are handled.
  Corrosive gas can cause corrosion of heat exchanger, breakage of 
plastic parts and etc. And combustible gas can cause fire.
• Do not install nor use the system close to the equipment that 
generates electromagnetic fields or high frequency harmonics.
  Equipment such as inverters, standby generators, medical high 
frequency equipments and telecommunication equipments can affect 
the system, and cause malfunctions and breakdowns. The system 
can also affect medical equipment and telecommunication equipment, 
and obstruct its function or cause jamming.
• Do not install the outdoor unit in a location where insects and 
small animals can inhabit.
  Insects and small animals can enter the electric parts and cause 
damage or fire. Instruct the user to keep the surroundings clean.
• Do not use the base flame for outdoor unit which is corroded 
or damaged due to long periods of operation.
  Using an old and damage base flame can cause the unit falling down 
and cause personal injury. 
• Do not use any materials other than a fuse with the correct 
rating in the location where fuses are to be used.
  Connecting the circuit with copper wire or other metal thread can 
cause unit failure and fire.
• Do not touch any buttons with wet hands.
  It can cause electric shocks.
• Do not touch any refrigerant pipes with your hands when the 
system is in operation.
  During operation the refrigerant pipes become extremely hot or 
extremely cold depending the operating condition, and it can cause 
burn injury or frost injury.
• 
Do not touch the suction or aluminum fin on the outdoor unit.
  This may cause injury.
• 
Do not put anything on the outdoor unit and operating unit.
  This may cause damage the objects or injury due to falling to the 
object.
Accessories for outdoor unit
• Model name and power source
• Refrigerant piping length
• Piping, wiring and miscellaneous small parts
• Indoor unit installation manual
Necessary tools for the installation work
Wrench key (Hexagon) [4m/m]
Vacuum pump
Vacuum pump adapter (Anti-reverse flow type)
(Designed specifically for R410A)
Gauge manifold (Designed specifically for R410A)
Charge hose (Designed specifically for R410A)
Flaring tool set (Designed specifically for R410A)
Gas leak detector (Designed specifically for R410A)
Gauge for projection adjustment
(Used when flare is made by using conventional flare tool)
9
10
11
12
13
14
15
16
Plus headed driver
Knife
Saw
Tape measure
Hammer
Spanner wrench
Torque wrench [14.0
~
62.0N·m (1.4
~
6.2kgf·m)]
Hole core drill (65mm in diameter)
1
2
3
4
5
6
7
8
Grommet (Heat 
pump type only)
Drain elbow (Heat pump type only)
Model 20, 25, 35
Model 50
Q’ty
1
4
1
1
2
Option parts
Sealing plate
Sleeve
Inclination plate
Putty
Drain hose (extension hose)
Piping cover
(for insulation of connection piping)
Q’ty
1
1
1
1
1
1
Check before installation work
a
b
c
d
e
f
Notabilia as a unit designed for R410A
• Do not use any refrigerant other than R410A. R410A will rise to pressure about 1.6 times higher than that of a conventional refrigerant.
 A cylinder containing R410A has a pink indication mark on the top.
• A unit designed for R410A has adopted a different size indoor unit operation valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake.
 The processed dimension of the flared part of a refrigerant pipe and a flare nut’s parallel side measurement have also been altered to raise strength against pressure.
 Accordingly, you are required to arrange dedicated R410A tools listed in the table on the right before installing or servicing this unit.
• Do not use a charge cylinder. The use of a charge cylinder will cause the refrigerant composition to change, which results in performance degradation.
• In charging refrigerant, always take it out from a cylinder in the liquid phase.
• All indoor units must be models designed exclusively for R410A. Check connectable indoor unit models in a catalog, etc. (A wrong indoor unit, if connected into the system, will impair proper system operation)










