Technical data
21
Pac k ag ed Ai r Con d i tion e rs
Control System
Outdoor unit
Internal/external Crossing
Indoor unit
Remote control
SL E Board
Network
options
X Y
X Y
X Y
A B
A B
Outdoor unit
Internal/external Crossing
Inside Inside Inside Inside
R R
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Inside
Inside Inside Inside
R R
SL E
Board
Outdoor unit
Internal/external Crossing
Inside
Inside Inside
R R
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Inside Inside
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Inside Inside
SL E
Board
Network
options
Wireless Kit
Wireless
remote control
Basic Connections Plural Controls by Multiple Remote Controls. Mixture of Multiple Units
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units Without Remote Control Wireless Kit
(3) Metal box dimension
85
40
35
30
90 5
100
70
22.5
2-ø6
SUPERLINK E BOARD (SC-ADN-E)
This board is used when conducting control of the single package (wired remote control unit) 1-type series using a network
option (SC-SL1N-E, SC-SL2N-E, etc).
(1) Functions
(a) Transmits the settings from the network option to the indoor units.
(b) Returns the priority indoor unit data in response to a data request from the network option.
(c) Inspects the error status of connected indoor units and transmits the inspection codes to the network option.
(d) A maximum of 16 units can be controlled (if in the same operation mode).
(2) Wiring connection diagram
Set up “000” to “127” using address switch on the SL E board.
• Transmit the information of plural “Master” units to the network.
• Transmit the abnormalities of the “Slave” units to the network.
Setting the plural “Master/Slave” units with the dip SW of the printed circuit board.
Setting the “Master/Slave” remote controls with the dip SW of the remote control board.
Set the SL E board dip SW to
“Master” SW3-1 ON.
The network option SLA-1-E,
SL1N-E is not allowed (This
will disturb switching of the
operation mode)
Control System
Start/stop control of up to 16 indoor units is
possible either individually or collectively. With
simple operations, you can effect centralized
control.
Centralized control of up to 64 indoor units. It
can allow connection with a weekly timer
without using any interface.
Easy operation realized with a large color LCD
and touch panel. Up to 128 indoor units can be
controlled, when three SUPERLINK-II systems
are connected.
SC-SL1N-E SC-SL2N-E
Central Control
SC-SL3N-AE/BE
Up to 96 groups (64 indoor unit x 2
SUPERLINK-II systems) are controlled
through an internet browser.
Up to 96 groups (64 indoor unit x 2
SUPERLINK-
II systems) are controlled
centrally from a BMS.
*
Additional engineering service cost etc. is required.
Up to 96 indoor units (48 indoor unit x 2)
are linked as an open network. Centrally
controlled through LonWorks.
SC-WGWN-A/B*
(SC-WGWN-B is with electric power calculation function)
PC windows central control
SC-BGWN-A*
(BACnet gateway)
BMS interface unit
SC-LGWN-A*
(LonWorks gateway)
SUPERLINK-SUPERLINK-
Connected to the remote controller terminals (no
polarity) (the length should be 600 m or shorter)
Connected to the terminals for
Superlink signal lines
MVVS 0.75 - 1.25mm
2
SL E board
OFF
SW3
SW1
LED2
Run
Abnormal
LED3
SW2
ON
A
B
X
Y
X
Y
A
B
Blue
Blue
Black
White
Master/Sub
address
Network address setting switches
[000]-(127)
200 m or shorter
300 m or shorter
400 m or shorter
600 m or shorter
0.5 mm
2
x 2 cores
0.75 mm
2
x 2 cores
1.25 mm
2
x 2 cores
2.0 mm
2
x 2 cores
SC-SL1N-E
SC-ADN-E
KX6 series
SC-ADN-E
RAC series
(SRK50/60ZHX-S)
SC-ADN-E
SC-BIKN-E
SC-SL2N-E
■ Control System
SUPERLINK-II
RC-E3 stores operation when an anomaly occurs and indicates the error on
the LCD. It also displays cumulative hours of the air conditioner and
compressor since commissioning.
Run hour meters to facilitate maintenance checking
Weekly timer function as standard
The temperature sensor is located in the top section of the
remote control unit. This has improved the sensitivity of the
remote controls heat sensor and permits more nely
controlled air conditioning.
Room temperature controlled by the remote control sensor
RC-E3 provides a 7day 24hr timer which allows programming of weekly
operating schedules to be registered. The user can specify up to four times a
day to start / stop the air conditioner. Temperature setting is also possible
with the timer.
Changeable range
Upper
limit
Lower
limit
20~30°C
(effective for heating operation)
18~26°C
(effective for non-heating operation)
The RC-E3 allows for the upper and lower
limits of a set temperature range to be
specied separately. By adjusting the set
temperature range you can ensure energy
saving air conditioning by avoiding
excessive heating or cooling.
Changeable set temperature range
The RC-E3 control allows access to service and maintenance data and easy to use comfort functions.
Improved Functionality